ClimAir INTERFACE+ Manuel D'installation page 18

Access
Holding
register
R
100
x
101
x
102
x
104
x
112
x
113
x
115
x
116
x
117
x
119
x
121
x
122
x
124
x
126
x
127
x
128
x
129
x
133
x
LW
Access
Holding
Register
R
200
201
x
202
x
204
x
205
x
210
x
211
x
212
x
220
x
221
x
222
x
223
x
w
Unlimited Write of Holding Register
LW
-
Limited Write (up to 10.000 times)
anaging
Parameter
name
w
LW
Modbus
Units
Devicetype
State
Error Code
Air Out Temperature
Unit Temperature
Reserved
OutAir SafetyTemperature
ActualRoomTemperature DS
Firing Rate
Flame Current
AnalogIn (IF)
Analogin override(simulated0-1OV
w
signal)
Reserved
TransportBlower
SuccessfulIgnitions
FailedIgnitions
Flame Count Failed
Burner
Hours
CH Mode
Description
w
Reserved
LW
HeatingModeOverride
LW
Ventilation
Mode
External Override
LW
Fan Override
ActualAir Out Setpoint
ActualRoomTemperature (HC)
ActualRoomTemperature Average(DS)
LW
DaySetpointTemperature
LW
Eco Setpoint Temperature
LW
Night Setpoint Temperature
LW
Frost Setpoint Temperature
eater
Automatic
Conversion
ontroller
Automatic
Conversion
Range
Bito: oc
OF
Bitl: bar/ psi
8 = Managing Air heater
See State table in 8xxMN Manual
See Error list
Depending onunits oc / OF(factor100)
Depending onunits oc / OF(factor100)
Depending onunits oc / OF(factor100)
Depending onunits oc / OF(factor100)
o. 100%
O..x resolution 0.1 uA
i.e. 10 means
1.0
0..9,0V represented as 0..900
0..9,OVrepresented as 0..900
0/100
0..100%
0..65536, r esolution16.Multiplyby 16to
getthenumberof successful i gnitions
See note 1
0..65536, resolution 1
0 65536, resolution 1
0 65536
hours
7
8
Range
0 = Room controller
1
Off
2 = Frost
Night
4 = Eco
Day
o = Off
I = On
O = No override
I = Override
active
O = No override
1 = Transport Fan in ventilation mode
[oc] (factor100)
[oc] IncaseDS is notconnectedthe
actual room temperature (HC) is shown
[oc] (factor100)
[oc] (factor100)
[oc] (factor100)
[oc] (factor100)
55