Wall Mounting - Baxi LUNA DUO-TEC 60 GA Notice D'installation

Masquer les pouces Voir aussi pour LUNA DUO-TEC 60 GA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Boiler weight exceeds 140 pounds (63.5 kg). Do not lift boiler onto wall without assistance
Lift boiler using chassis. Do not use front jacket, vent piping, water or gas fittings to lift boiler as it may cause
damage to the boiler.
Use caution when tightening and fitting to pipe boiler's threaded fittings. Boiler's internal piping can be damaged
if subjected to excessive torque.

4.3 Wall Mounting

1.
Decide position of boiler on the wall allowing for all required clearances and flue terminal position.
2.
Tape template to the wall. Ensure template is level and upright. Mark position of holes for boiler mounting bracket and
plumbing connections.
3.
Rear exit flue - mark position of hole for flue.
4.
Side exit flue - mark horizontal center line of flue across the wall to side wall, then along side wall (ensure lines are parallel and
sloped properly towards the boiler, refer to section 6. This will give position of center of hole for flue.
5.
Cut hole in wall for coaxial flue : 5 5/16" [135 mm] diameter
6.
Pre-pipe supply and return water connections with factory fittings before wall mounting.
7.
Mount boiler on wall using wall mounting bracket included with unit.
8.
Adjust the position of the boiler verify it is level.
FIGURE 4-1 Wall Mount Bracket
(Included)
!
CAUTION
NOTICE
Center brackets. Avoid
overhang on sides of wall
mount bracket.
Use four (4) predrilled
holes for mounting bracket
to wall
13
240012485 REV A [12/30/2018]

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Luna duo-tec 1.48 ga

Table des Matières