Baxi LUNA DUO-TEC 60 GA Notice D'installation page 120

Masquer les pouces Voir aussi pour LUNA DUO-TEC 60 GA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Near boiler piping
Vent
Piping
Safety Relief Valve
Visual
Functional
System
Temperatures
Connections
Electrical
Smoke and Co detector
Circuit Breakers
Combustion Chamber
Chamber/
Burner
Spark Electrode
Flame Sensor
Neutralizer
Condensate
Condensate pipe/trap
Pressure
Pressure drop
Gas
Leaks
Combustion
CO/CO₂ Levels
Safety
All Sensors
Check List
Final
Inspection
Homeowner
* Continue inspections beyond 4th year. Maintenance should continue annually for the life of the boiler to ensure
safe worry free operation.
Required Inspection Schedule
To Be Completed By
Qualified Service Technician
Inspection Items
Check boiler and system piping for any sign of
leakage, verify pipes are properly supported.
Check condition of all vent pipes and joints. Verify
vent piping terminations are free of obstructions
and blockages.
Follow safety relief valve manufacturer's
instructions for maintenance and repair. Verify
dischage pipe properly installed per IOM.
Do full visual inspection of ALL system
components.
Test all functions of the system (heat and safety)
Verify safe settings on boiler or anti-scald valve.
Verify programmed temperature settings.
Check wire connection. Verify connections are
tight.
Verify devices are installed and working properly.
Change batteries if necessary.
Check that circuit breaker is clearly labeled and
operates correctly.
Check burner and combustion chamber. Clean
following directions in maintenance section of IOM.
Replace gaskets whenever checking combustion
chamber.
Clean. Set gap according to IOM directions. Clean
electrode with plumbers cloth to remove oxides.
Clean sensor.
Check condensate neutralizer - replace if
necessary.
Disconnect condensate pipe. Clean out any dirt
or accumulation. Fill with water level of outlet
and reinstall. NOTE: verify flow of condensate,
make sure hose is properly connected during final
inspection.
Measure incoming gas pressure per IOM.
Measure drop in pressure on light off verify with
IOM.
Check gas piping. Test for leaks and signs of aging.
Make sure all pipes are properly supported.
Check CO and CO₂ level in exhaust. See Start-up
Procedures for ranges. Record at high and low fire.
Check continuity of all sensors. Replace if corroded.
Verify all connections through ohms reading.
Verify you have completed entire check list.
Review findings and service with Homeowner.
Date Completed
Year
Year
Year
1
2
PN 240011561 REV B, [09/19/2018]