Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. Specifications

MODEL
CAPACITY*
INPUT
Input voltage
Frequency range
Power factor
OUTPUT
Output voltage
Voltage Regulation
Frequency range
Frequency range (batt mode)
Current Crest Ratio
Harmonic Distortion
Transfer
AC Mode to Batt. Mode
Time
Inverter to Bypass
Waveform
EFFICIENCY
AC Mode
Battery Mode
BATTERY
Battery type
Number
Recharge Time
Charging Current
Charging voltage
Backup time
PHYSICAL CHARACTERISTICS
Dimension, LxlxH (mm)
Net weight (kgs)
INDICATORS
LED
Alarms
BYPASS
Bypass static
Bypass manual
ENVIRONMENT
Humidity
Noise level
MANAGEMENT & COMMUNICATION
Communication port
Software
NORMS***
Standard
EMC
LVD
SALES INFORMATIONS***
Warranty
Gencods (IEC models)
Gencods (NEMA LV models)
Gencods (NEMA HV models)
* Derate to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC
**Low voltage (110V) and High voltage (230V) are different products.
***LV products (110/120V) comply with same test reports level as HV products (220/230V), for which those CE tests were performed.
Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 03 16 AA AA 204 08
E4 VALUE 1000
1000 VA / 800 W
[100/110/115/120/127VAC] or [200/208/220/230/240VAC]**
[100/110/115/120/127VAC] or [200/208/220/230/240VAC]**
<= 3% THD (linear load); <= 6% THD (non-linear load)
88%
83%
12 V / 9 Ah
2
4 hours recover to 90% capacity (Typical)
27.4 VDC ± 1%
From 5 to 30 min. depending on the connected load
282 x 145 x 220
8.64
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator.
Battery mode, Low battery, Overload, Fault
20-90 % RH @ 0- 40°C (non-condensing)
Infopower included software (Supports Windows® 98/2000/2003/XP/Vista/2008, Windows©
EN 62040-2:2006+AC:2006; EN61000-3-2:2006+A1:2009+A2:2009
3700085 67417 8
3700085 68394 1
3700085 68501 3
E4 VALUE 1500
E4 VALUE 2000
1500 VA / 1600 W
2000 VA / 1600 W
40Hz ~ 70 Hz
≧ 0.99 @ 100% load
±1% (Batt. Mode)
47 ~ 53 Hz ou 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
3:1
Zero
4 ms (Typical)
pure sinusoïdale
89%
87%
12 V / 9 Ah
4
1.0 A
54.7 VDC ±1%
397 x 145 x 235
16.10
Yes
Optional
Less than 50dBA @ 1 Meter
RS232
7,8, 10, Linux, and MAC)
CE RoHS
EN 62040-1:2008+A1:2013
2 years
3700085 67425 3
3700085 67418 5
3700085 68398 9
3700085 68395 8
3700085 68502 0
3700085 68503 7
E4 VALUE 3000
3000 VA / 2400 W
90%
88%
12 V / 9 Ah
6
82.1 VDC ±1%
421 x 190 x 335
25.20
3700085 67419 2
3700085 68396 5
3700085 68504 4
34