Charging station
+
-
SG
RS-485
External control
(dry contact)
NC
Energy meter
36 / 68
External control device
•
Connect a dry contact module for override mode to the ter-
minals 4 and 5. Remove the jumper from the pre-installed
connector.
Note! If you do not connect a dry contact module to the charg-
ing station, do not remove the jumper or change the related
settings in the Charger Control application.
•
The default setting for external control is NC (normally
closed).
When the contact is closed, charging is allowed.
When the contact is opened, charging is not allowed.
•
If you install the external control as NO (normally open),
change the settings accordingly in the Charger Control ap-
plication.
External control
Normally closed
(NC)
Normally open
(NO)
LERAK131B-FRENIT/20230502
Switch
Charging
Allowed
Not allowed
Allowed
Not allowed