Adeunis RF sigfox TEMP Guide Utilisateur page 49

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

sigfox TEMP- Guide utilisateur / User guide version V1.2.0
Explanation of thresholds and hysteresis:
The period of monitoring by the sensors is equal to the period of acquisition (register 317) divided by the super-sampling factor (register 318).
The settings associated with this mode of operation are:
• The transmission periodicity (zero in this usage situation) (register 301)
• Potential user identifiers for the sensors (registers 302 and 304).
• The configuration of the events (registers 303 and 305).
• The high alarm threshold for the internal sensor (register 309).
• The high alarm hysteresis for the internal sensor (register 310).
• The low alarm threshold for the internal sensor (register 311).
• The low alarm hysteresis for the internal sensor (register 312).
• The high alarm threshold for the external sensor (register 313).
• The high alarm hysteresis for the external sensor (register 314).
• The low alarm threshold for the external sensor (register 315).
• The low alarm hysteresis for the external sensor (register 316).
• The acquisition period (register 317).
• The super-sampling factor (register 318).
A complete list of the registers can be found in paragraph 3.4.
High alarm enabling
Low alarm enabling
High alarm disabling
high threshold
High threshold -
high threshold hysteresis
Sensor value
Low threshold +
low threshold hysteresis
Low threshold
Low alarm disabling
Page
EN
49
of 72

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8181ba

Table des Matières