Caractéristiques techniques IR427
Coordination de l´isolement selon IEC 60664-1 / IEC 60664-3
Tension assignée ..................................................................................................................... 250 V
Qualité diélectrique / degré de pollution ............................................................................ 4 kV / III
Séparation sûre (isolation renforcée) entre .......................................................................................
................................................................................ (L1, L2, E, KE, 1, 2, 3, 4, Z, Z/k, I) - (11, 12, 14)
Essai diélectrique selon IEC 61010-1 ................................................................................... 2,21 kV
Tension d´alimentation
Tension d´alimentation U
...................................................................................................... = U
s
Consommation propre ..........................................................................................................
Réseau IT surveillé
Tension réseau U
....................................................................................................... AC 70...264 V
n
Fréquence nominale f
.................................................................................................... 47...63 Hz
n
Surveillance de l´isolement
Valeur de seuil R
.................................................................................... 50...500 kΩ (50 kΩ)*
an
Tolérance du seuil ................................................................................................................. ±10 %
Hystérèse ................................................................................................................................. 25 %
Temps de réponse t
pour R
= 0,5 x R
an
F
an
Capacité de fuite C
.................................................................................................................... 5 μF
e
Circuit de mesure
Tension de mesure U
.......................................................................................................... ±12 V
m
= 0 Ω) ..............................................................................
Courant de mesure I
(pour R
m
F
Résistance interne DC R
...................................................................................................
i
Impédance Z
pour 50 Hz .................................................................................................
i
Tension DC maxi étrangère U
.....................................................................................
fg
Surveillance du courant de charge
Valeur de seuil paramétrable ................................................................................. 5...50 A (7 A)*
Tolérance du seuil .................................................................................................................. ± 5 %
Hystérèse..................................................................................................................................... 4 %
Valeurs de réglage mesure du courant de charge :
Transformateur 3150 VA ....... 4000 VA ....... 5000 VA ........ 6300 VA ....... 8000 VA ..... 10000 VA
I
.................. 14 A .............. 18 A .............. 22 A .............. 28 A ............. 35 A ............. 45 A
alarm 1~
Surveillance de la température
Valeur de seuil (valeur fixe) ..................................................................................................... 4 kΩ
Valeur de relâchement (valeur fixe) ..................................................................................... 1,6 kΩ
Sonde selon DIN 44081 ............................................................................................. max. 6 en série
Affichage, mémoire
Affichage écran à cristaux liquides, multi fonctions, non rétroéclairé
Valeur mesurée résistance d´isolement ................................................................ 10 kΩ...1 MΩ
Erreur maximale de fonctionnement ................................................................... ± 10 %, ± 2 kΩ
Valeur mesurée courant de charge (en % de la valeur de seuil préréglée) ........... 10 %...199 %
Erreur maximale de fonctionnement ..................................................................... ± 5 %, ± 0,2 A
Mot de passe .......................................................................................... on, off / 0...999 (off, 0)*
interface pour MK7
Longueur du câble, torsadé par paire, blindé ....................................................................
Câble recommandé .......................................................... min. J-Y(St)Y 2x2 x 0,6; blindage sur PE
Alimentation (borne 1 et 2) :
U
....................................................................................................................................... DC 24 V
aus
I
(max. 4 MK7) .................................................................................................................. 80 mA
max
Communication (bornes 3 et 4) :
Interface / protocole .................................................................. RS-485 / propriétaire, pas de BMS
Résistance terminale ......................................................... 120 Ω (0,25 W), interne, commutable
Interfaces pour tore de détection STW2 et sonde de température
Longueurs du câble :
unifilaire > 0,5 mm² ...............................................................................................................
unifilaire, torsadé> 0,5 mm² ...............................................................................................
torsadé par paire, blindé > 0,5 mm² ...................................................................................
Câble recommandé ............................................................... min. J-Y(St)Y 2x0,6; blindage sur PE
TBP201007fren / 04.2011
et C
= 0,5 μF.......................................................
e
Technical data IR427
Insulation coordination acc. to IEC 60664-1 / IEC 60664-3
Rated insulation voltage .......................................................................................................... 250 V
Rated impulse voltage/pollution degree ............................................................................ 4 kV / III
Protective separation (reinforced insulation) between ....................................................................
............................................................................... (L1, L2, E, KE, 1, 2, 3, 4, Z, Z/k, I) - (11, 12, 14)
Voltage test according to IEC 61010-1 ................................................................................ 2.21 kV
Supply voltage
Supply voltage U
...................................................................................................................... = U
n
S
≤
4 VA
Power consumption ...............................................................................................................
IT system being monitored
Nominal system voltage U
Nominal frequency f
Insulation monitoring
Response value R
an
Relative percentage error ..................................................................................................... ±10 %
Hysteresis.................................................................................................................................. 25 %
≤
5 s
Response time t
at R
an
Permissible system leakage capacitance C
Measuring circuit
Measuring voltage U
≤
50 μA
Measuring current I
≥
240 kΩ
Internal DC resistance R
≥
200 kΩ
Impedance Z
, at 50 Hz .....................................................................................................
i
≤
DC 300 V
Extraneous DC voltage U
Load current monitoring
Response value, adjustable ................................................................................... 5...50 A (7 A)*
Relative percentage error ....................................................................................................... ±5 %
Hysteresis ..................................................................................................................................... 4%
Setting value load current measurement:
Transformer ..... 3150 VA ....... 4000 VA ....... 5000 VA ....... 6300 VA ....... 8000 VA ..... 10000 VA
I
...................14 A .............. 18 A ............. 22 A ............. 28 A .............. 35 A .............. 45 A
alarm 1~
Temperature monitoring
Response value (fixed value) ................................................................................................... 4 kΩ
Release value (fixed value) .................................................................................................... 1.6 kΩ
PTC thermistors acc. to DIN 44081 .......................................................................... max. 6 in series
Displays, memory
LC display ...................................................................................... multifunctional, not illuminated
Measured value insulation resistance ................................................................... 10 kΩ...1 MΩ
Operating error ...................................................................................................... ±10 %, ± 2 kΩ
Measured value load current (as % of the set response value) ............................. 10 %...199 %
Operating error ......................................................................................................... ±5 %, ±0.2 A
Password ................................................................................................. on, off / 0...999 (off, 0)*
Interface for MK7
≤
200 m
Cable length, twisted pairs, shielded .................................................................................
Recommended cable ....................... min. J-Y(St)Y 2x2 x 0.6; shield on one side connected to PE
Power supply (terminals 1 and 2):
U
...................................................................................................................................... DC 24 V
aus
I
(max. 4 MK7) ................................................................................................................. 80 mA
max
Communication (terminal 3 and 4):
Interface/protocol ............................................................ RS-485 / proprietary interface (no BMS)
Terminating resistor ............................................................ 120 Ω (0.25 W), internal, switchable
Interfaces for STW2 measuring current transformer and tem-
perature sensor
≤
1 m
Cable lengths:
≤
10 m
Single wire > 0.5 mm² ..........................................................................................................
≤
40 m
Single wire, twisted > 0.5 mm² ..........................................................................................
twisted pair, shielded > 0.5 mm² .......................................................................................
Recommended cable ............................. min. J-Y(St)Y 2x0.6, shield on one side connected to PE
A-ISOMETER® IR427 plus MK7
........................................................................................ AC 70...264 V
n
....................................................................................................... 47...63 Hz
n
................................................................................... 50...500 kΩ (50 kΩ)*
= 0.5 x R
and C
= 0.5 μF .............................................................
F
an
e
............................................................................. 5 μF
e
........................................................................................................... ±12 V
m
= 0 Ω) ...................................................................................
(at R
m
F
...................................................................................................
i
.............................................................................................
fg
n
≤
4 VA
≤
5 s
≤
50 μA
≥
240 kΩ
≥
200 kΩ
≤
DC 300 V
≤
200 m
≤
1 m
≤
10 m
≤
40 m
10