Unplug the UPS prior to cleaning and do not use liquid or detergent spray.
WARNING : This is a C2 category UPS product. In a residential environment, this product
may cause radio interference, in which case the user many be required to take additional
measures.
Please replace the fuse or circuit breaker only with the same type and amperage in order
to avoid fire hazards.
CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT
TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
6.
Software download & Installation
Please follow steps below to download and install monitoring software:
1) Go to the website https://www.infosec-ups.com/en/infopower
2) Choose your required OS to download the software.
3) Follow the on-screen instructions to install the software.
4) When your computer restarts, the monitoring software will appear
as an orange plug icon located in the system tray, near the clock.
7.
Trouble shooting
Use the table below to solve minor problems.
Problem
No words display on
the front panel.
Alarm continuously
sounds when the
mains is normal.
When power fails,
back-up time is
shorten.
The mains is normal
Bu the unit is on
battery mode.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 09 24 103 59 203 14
Possible Cause
Low battery
Battery fault
The UPS is not turned on
The UPS is overload
The UPS is overload
Battery voltage is too low
Battery defect. It might be due to
high temperature operation envi-
ronment, or improper operation to
battery
Power cord is loose
Solutions
Charge the UPS at least 6 hours
Replace the battery with the same type
of battery
Press the power switch again to turn on
the UPS
Remove some loads first. Before recon-
necting equipment, please verify that
the load matches the UPS capability
specified in the specs
Remove some critical load
Charge the UPS at least 6 hours
Replace the battery with the same type
of battery
Reconnect the power cord properly
English version