Changing settings

Symbol
Name
ON
OFF
Dim up
Dim down
Automatic mode
Set current light level
Light level low
Light level middle
Light level high
Bright Out ON
(default)
Bright Out OFF
PIR inactive
PIR off only
3 EN
LINETIK lighting management
LINETIK can be parametrised using an IR remote control:
Description
Switch-on of the luminaire
Switch-off of the luminaire
Increase current dim level
Reduce current dim level
Luminaire switches on (if previously in standby)
→ light regulation is started (if not permanently deactivated)
Store the brightness level currently measured by the sensor as target
value for constant light control (press button >3s)
Setting of the ambient light control to a value of approx. 150 lx
Setting of the ambient light control to a value of approx. 300 lx
Setting of the ambient light control to a value of approx. 500 lx
Activate Bright Out: The lighting switches off if the measured light
value exceeds 150% of the desired value for more than 15 minutes.
The lighting switches on again if the measured light value is below
100% of the desired value.
Deactivate Bright Out: The lighting always stays switched on
irrespective of the measured light value.
Set motion detection inactive. The run-on time is also set to "infinite"
Motion detection only reacts to absence
→ The lighting must be switched on manually (momentary-action
switch, remote control).
→ The lighting switches off automatically during absence. The run-on
time is also set to 20 minutes
(Article no. 28000257
should be ordered separately)