Here you can set the configuration (Single Unit, System or Multi Channel) in which the 1873-ESM is to be
operated, see page 7. The selection changes the menu, since only the menu items relevant for the ap-
plication are displayed.
Date/Time (System, Multi Channel)
If the device is operated in the System or Multi Channel application, the date and time must be set cor-
rectly. (If there is an internet connection, the device receives the date and time from the internet. If the
device is put into operation for the first time and there is no internet connection, check whether the date
and time are correct. The power reserve only keeps this data for a limited time if the device has no power
supply.)
Sensor type (Single Unit, System)
The factory setting for the sensor type is "to be defined". Select the sensor type according to the con-
nected sensor.
In a Multi Channel configuration, the sensor type must be set for each channel.
Server communication active (System, Multi Channel)
If tekmar's TAV Server is to be used, communication must be activated here.
Moisture treshold
It should be checked whether the factory-set moisture threshold matches the sensor used and its env-
ironment. Proceed as follows:
1.
The sensor must be dry
2.
Start a test measurement.
Single unit and system
Multi channel
3.
Add 1.0 to 2.0 to the determined moisture value depending on the desired sensitivity and set this
value as the moisture threshold.
Single unit
system
Multi channel