Télécharger Imprimer la page

Autosen AD003 Notice D'utilisation page 52

Publicité

Les langues disponibles

Les langues disponibles

7.4.6 C.ASP/C.AEP - customer-specific analogue start/end point
Settings for scaled display values�
The parameters are only displayed when [ScAL] is set to [cccc], [ccc�c], [cc�cc] or
[c�ccc]�
C�ASP value: -746 ��� 9745 corresponds to 4 mA�
C�AEP value: -366 ��� 9366 corresponds to 20 mA�
If a scaling is set via [ScAL], the C�AEP value also has to be adapted
accordingly:
With [ScAL] = [ccc.c] → C.AEP value x 10
With [ScAL] = [cc.cc] → C.AEP value x 100
With [ScAL] = [c.ccc] → C.AEP value x 1000
All displayed current values are interpolated based on a 2-point approxima-
tion ([SP1]+[rP1], [FH1]+[FL1], [cFH]+[cFL], [Lo]+[Hi])�
IO-Link process data and parameters are not influenced by scaling�
~ 9999
C.AEP
4
3.6
C.ASP
-746
~ 999
C�ASP = min� value
C�AEP = max� value
52
9366
C.ASP
20
[mA]
21
C.AEP
C�ASP = max� value
C�AEP = min� value
~ 9999
9745
4
3.6
~ 999
20
[mA]
21
-366

Publicité