Télécharger Imprimer la page

Siemens IL SOLE REV 24 Manuel D'installation page 9

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 12
Mounting notes REV24..
DE
1
Placement of unit
EN
·
The REV24.. should be mounted in the main living room (for wall
mounting, refer to Figs. B through E)
FR
·
The REV24.. must be located such that it can acquire the room
temperature as accurately as possible, without getting affected by
direct solar radiation or other heat or refrigeration sources
IT
NL
ES
PT
CS
HU
Commissioning
PL
1
Switching on the REV24..
SV
·
Remove the black battery transit tab (Fig. F); as soon as the tab is
removed, the unit is ready to operate
(also refer to operating instructions)
FI
2
Selecting the language
DA
·
When starting up, the display shows the type of controller at top left
and "THANK YOU ..." in all available languages on the text line
TR
Configuration and function check REV24..
EL
1
Configuration
1.1
DIP switches
ON /
Sensor calibration on
See
1.1.1
Sensor calibration off
Setpoint limitation
16...35 °C
1.1.2
Setpoint limitation
3...35 °C
Temperature display °F
1.1.3
Temperature display °C
PID self-learning
PID 6
1.1.4
PID12
2-Point
1.1.9
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button
(also refer to Fig. 8). Otherwise, the previous settings will be maintained!
6/50
min.
10 cm
OFF
1
2
DIP switch reset
Factory setting: All DIP switches
2
Mounting
·
Refer to Figs. A through E
3
Checking the wiring
For electrical connections, refer to "Connection diagram".
Note:
Do not use stranded wires, only solid wires
or stranded wires with ferrules!
4
Notes
·
The local regulations for electrical installations must be complied
with
·
If the reference room is equipped with thermostatic radiator
valves, they must be set to their fully open position
·
External preliminary protection with max. C 10 A circuit breaker is
required in all cases
·
Press one of the buttons to stop the running display. The choice
of languages starts with "ENGLISH" (factory setting). Press
or
move the slider to confirm the selected language (also refer to
Fig. G)
3
4
5
6
7
ON
1
2
3
4
5
6
2015-02-27
until the language you require appears. Press
8
9
10
Periodic pump run on
Periodic pump run off
Optimum start
control:
1 h/°C
Optimum start
control:
¼ h/°C
Optimum start
control:
½ h/°C
Optimum start
control: Off
(Cooling on)
(Heating on)
Quartz
Radio clock
7
8
9
OFF
or
See
1.1.5
1.1.6
1.1.7
1.1.8
1.1.9
CE1G2205xx

Publicité

loading