1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currentl1y acquired
blinks. Press
or
to make a recalibration of max. ± 5 °C. To
save the entry, set the DIP switch to OFF and press the DIP switch
reset button (also refer to Fig.
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF:
Setpoint limitation 3...35 °C (factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON:
Temperature display in °F
DIP switch OFF:
Temperature display in °C (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON:
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF:
For fast controlled systems, applications at locations with
great temperature variations.
DIP switch 4 OFF and 5 ON:
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF:
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer
off periods. Periodic pump run is activated for 3 minutes every 24
hours at 12:00 (display showing symbol
DIP switch ON:
Periodic pump run on (also refer to Fig.
DIP switch OFF:
Periodic pump run off (factory setting)
Save the entry by pressing the DIP switch reset button.
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
press simultaneously
and
level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Code
00
Basic settings
01
02
10
LCD settings
11
12
30
Clock settings
31
32
CE1G2205xx
).
PID self-learning
PID 6
PID 12
2-Point
).
for 3 seconds, release
and keep
on display (also refer to Fig. G).
Name
Language
Sensor calibration
Switching differential 2-point
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal received from
Frankfurt (Central European Time CET)
(refer to Note 1)
Start of summer time (refer to Note 2)
End of summer time (refer to Note 3)
1.1.6 Optimum start control: DIP switches 7 and 8
Optimum start control shifts switch on point P.1 such that the adjusted
setpoint will be reached at the required point in time. The setting
depends on the type of controlled system, that is, on heat transmission
(piping network, radiators), building dynamics (building mass,
insulation) and heat output (boiler output, flow temperature)
(also refer to graph in Fig.
DIP switch 7 ON and 8 ON:
1 h/°C
DIP switch 7 ON and 8 OFF:
¼ h/°C
DIP switch 7 OFF and 8 ON:
½ h/°C
DIP switch 7 OFF and 8 OFF:
OFF
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig. .
t
Temperature (°C)
t
Forward shift of switch on point (h)
TRx
Actual value of room temperature
Pon
Start point for optimum start control
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
DIP switch 9 OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.8 Radio clock: DIP switch 10
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
)
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3 seconds,
depressed for another 3 seconds. This enables you to access the expert
.
Factory setting
English
off
0.5 °C
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
2015-02-27
/ 1.1.6
).
For slow controlled systems
For fast controlled systems
For medium controlled systems
Off, no impact (factory setting)
:
Cooling mode
Heating mode (factory setting)
).
quartz
Clock runs on built-in
Time signal DCF77 from Frankfurt
).
and
. Confirm the
Your setting
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL