Télécharger Imprimer la page

Eaton ModularEasy 9PX 5000i HotSwap Manuel D'installation Et D'utilisateur page 21

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 29
4. Power cables connection
4.3 9PXMEZ11Ki - with separate Normal and Bypass AC source
1. Slide the ModularEasy Bypass input cover
2. Punch the two Bypass Input knockouts of the ModularEasy Bypass Input cover
small provided cable glands inside.
3. Insert a power cable through each cable glands of the ModularEasy Bypass Input cover
provided in the packaging. It is recommended to use a cable with 3 conductors, 50 cm in length and with
a minimum wire size rating : 10 mm² (8 AWG).
4. Connect the wires to the "Input BP" terminal blocks of the ModularEasy Bypass Input cover
5. Tighten the cable gland.
6. Slide back and secure the ModularEasy Bypass Input cover
7. Connect the 4 integrated power cables and the 2 previously installed Bypass Input power cables to the
UPS1 and UPS2 I/O terminal blocks.
Following color coding on the cables and the UPS I/O cover (blue for UPS Input / red for UPS Output /
yellow for UPS Input Bypass) – refer to the UPS user manual to check the UPS terminal blocks connection.
Do not forget to remove the Input Bypass AC jumper on the UPS.
8. Connect the ModularEasy detection cable
Manual).
9. Slide the ModularEasy I/O cover
blocks.
Page 18
after removing the two screws, to access the ModularEasy terminal
3
Before
after removing the screw.
5
with the screw.
5
to the specific UPS connector (refer to the UPS User
2
and insert the two
5
. Cables are not
5
5
After
.
614-09354-01_EN

Publicité

loading