Protection unit MP2.10
tsd
m
s
I²t=k
NEUTRAL protection (if present)
N= NEUTRAL protection setting (for Is, Isd and Ii)
Example of setting N:
N
%
1. Navigate the menu until you reach the page of N
2. Push on the encoder
3. Type the password if necessary
4. The N symbol blinks with T=0.5 sec
5. Starting from the set value, rotate the encoder until reaching the desired value with steps of 50%
(OFF-50%- 1 00%- 1 50%-200%).
6. Push on the encoder to confirm.
7 . The N icon stops blinking.
1
LEVEL
st
Protection
Neutral protection
Current adjustment (3 positions)
N=OFF 50% 100% 150% 200%
Neutral setting by default
PROTECTION
Neutral
N
%
tg
m
s
I²t=k
2
LEVEL
nd
Neutral (if any)
I= 400 A 800 A 1200 A
Isd 1600 3100 A 4800 A
IiN 1600 3100 A 4800 A
DMX³ 1600
MP2.10/MP4.10
LI/LSI/LSIg
4P: 100 (MAX) - SX
3P: not adjustable
3
LEVEL
rd
Protection = ON/OFF
N = 50%-200%
(depends on settings)
DMX 2500 SP
MP2.10/MP4.10
LI/LSI/LSIg
4P: 100 (MAX) - SX
3P: not adjustable
61