DIEL MT 200 E Manuel D'instruction page 73

Centrale qui sert à contrôler les températures du transformateur / moteur au moyen de sondes pt100 à 3 fils sur 4 canaux maximum

Publicité

Les langues disponibles
  • FR

Les langues disponibles

• Register 9 Status fault channel CH1 to CH4: bit 0 to bit 3
0
Fault not active
1
Fault active
• Register 10 Status relay channel Fan (bit 3) Fault (bit 2) Pre-alarm (bit 1) Alarm (bit 0)
0
Relay not active
1
Relay active
• Register 21 Status channel CH1 to CH4: bit 0 to bit 3
0
Channel disable
1
Channel enable
• Register 22 Status fan active channel Fan 1 to Fan 4: bit 0 to bit 3
0
Request fan not active
1
Request fan active
Notes
Defeult ip address 192.168.1.205 subnet mask 255.255.225.0 gateway 192.168.1.1.
Registers 1 to 8 and 23 to 38 format: 16 bit signed short (-32767 / +32767).
Registers 1 to 8 and 23 to 38 have scale factor 100.
Supported MODBUS-TCP standard functions:
03x Read holding register, 04x Read input register
06 Write register, 16x Write multi registers.
MT 200 E
- 73 -
TAB 2