Installation, Maintenance, and Repair Manual
Series 957, 957RPDA, LF957RPDA
Reduced Pressure Zone Assemblies
Reduced Pressure Detector Assemblies
2
" – 10"
1
2
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
WARNING
!
Local building or plumbing codes may require modifications
to the information provided. You are required to consult
the local building and plumbing codes prior to installa-
tion. If the information provided here is not consistent
with local building or plumbing codes, the local codes
should be followed. This product must be installed by
a licensed contractor in accordance with local codes
and ordinances.
!
WARNING
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes,
but at least once per year or more as service conditions war-
rant. All products must be retested once maintenance has
been performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective
for the service intended. Regular checking and cleaning of
the product's internal and external components helps assure
maximum life and proper product function.
!
WARNING
This device must be tested periodically in compliance with
local codes, but at least once per year or more as service
conditions warrant. If installed on a fire sprinkler system, all
mechanical checks, such as alarm checks and backflow
preventers, should be flow tested and inspected internally in
accordance with NFPA 13 and NFPA 25.
!
WARNING
Do not impede or prevent sleeve movement by installing riser
cradle clamps or other obstructive elements on or around the
sleeve. Sleeve movement is required to service the backflow.
Testing
For field testing procedure, refer to Watts installation sheets
IS-TK-DL, IS-TK-9A, IS-TK-99E and IS-TK-99D at www.watts.com.
For technical assistance, contact your local Watts representative.
Series 957, 957RPDA, and LF957RPDA each include a flood
sensor on the relief valve to detect excessive discharge and
trigger notification of potential flood events.
NOTICE
An add-on connection kit is required to activate the flood sensor.
Without the connection kit, the sensor is a passive component that
has no communication with any other device. (A retrofit connection
kit is also available for existing installations. See "Add-on and Retrofit
Sensor Connection Kits," for ordering details.)
NOTICE
Use of the flood sensor does not replace the need to comply with
all required instructions, codes, and regulations related to instal-
lation, operation, and maintenance of this product, including the
need to provide proper drainage in the event of a discharge.
Watts is not responsible for the failure of alerts due to connectivity
issues, power outages, or improper installation.
NOTICE
For Australia and New Zealand: Pipeline strainers should be
installed between the upstream shutoff valve and the inlet of the
backflow preventer.
Fittings such as end connectors intended to join alternative pipe
systems made from other materials (such as plastics) shall also
conform to the relevant dimensional and performance requirements
of the appropriate Australian, New Zealand, or joint Australian–
New Zealand Standard for the alternative pipe system.
RP/IS-957/957RPDA
957-OSY with Flood Sensor
Table des Matières
loading

Sommaire des Matières pour Watts 957 Serie

  • Page 9: Ensembles Pour Zones À Pression Réduite Dispositifs De Pression Réduite

    éléments obstructifs sur ou autour du manchon. Le mouvement du Watts n’est pas responsable de la défaillance des alertes due à des manchon est nécessaire pour le service de refoulement.
  • Page 10  po – charge par l’usage d’un raccord à lame d’air et d’une conduite 10 po (6,4 cm à 25,4 cm) d’évacuation indirecte préfabriquée Watts. Un drain de sol de taille l/min gpm 1330 350 appropriée pour la décharge doit être installé en cas de décharge excessive.
  • Page 11: Entretien Des Modules De Clapet

    Figure E Figure F AVERTISSEMENT Avant de procéder à l’entretien d’une vanne Watts, il est obligatoire 5. Répétez l’étape 4 pour retirer le module de clapet n° 2. (Pour l’entretien d’arrêter le système d’eau en fermant les robinets d’arrêt d’entrée des clapets de 6 po [15,2 cm], voir les instructions d’entretien pour les et de sortie.
  • Page 12 • Clé à fourche ou à douille de  po (1,9 cm) Instructions AVERTISSEMENT Avant de procéder à l’entretien d’une vanne Watts, mettez le système d’eau à l’arrêt en fermant les robinets d’arrêt d’entrée et de sortie. Cette opération est obligatoire. Une fois les robinets Figure B d’arrêt fermées, ouvrir les robinets d’essai n° 2, n° 3 et n° 4 pour...
  • Page 13: Entretien De La Soupape De Décharge

    Entretien de la soupape de décharge Figure A AVERTISSEMENT Avant de procéder à l’entretien de la soupape de décharge, il est obligatoire d’arrêter le système d’eau en fermant les robinets d’arrêt d’entrée et de sortie et de libérer la pression dans l’ensemble en ouvrant les robinets d’essai n° 2, n° 3 et n° 4.
  • Page 14: Dépannage

    Pour les trousses de réparation et les pièces, reportez-vous à la liste de prix des trousses de Membrane Vis, couvercle réparation et des pièces de rechange pour les produits anti-refoulement PL-RP-BPD sur le site Ensemble de www.watts.com. plaque de recouvrement Dépannage SYMPTÔME CAUSE SOLUTION La soupape de décharge évacue l’eau lorsque le système...
  • Page 15 Trousses de connexion de capteur complémentaire et de modernisation pour les systèmes de gestion de bâtiment N° DE PIÈCE TROUSSE COMPLÉMENTAIRE/DE MODERNISATION DESCRIPTION 88009418 FP-BF-BMS Comprend un module d’activation de capteur avec câble, un fil de mise à la terre, Trousse de connexion de capteur BMS et un adaptateur d’alimentation.
  • Page 16 Garantie limitée : Watts (la « Société ») garantit que chacun de ses produits est exempt de vice de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à compter de la date d’expédition d’origine. Si une telle défaillance devait se produire au cours de la période sous garantie, la Société pourra, à sa discrétion, remplacer le produit ou le remettre en état, sans frais.