EVO - OnBoard
A
B
C
Press Enter to switch
M08
Manual Controls
D
E
F
Ref. #
P/N
Designed by
Checked by
Approved by - date
File name
IAN
ROGER
2023-03-17
HSS306080CTRL
1
1
2
Setup Done
YES
ENANLE DEVICE
Default Request
NO
EEV n°1
Valve: CAREL E2Vu
SUPERPAREMETERS
Main Regulation:
AC OR CHILLER WITH
BLDC COMPRESSOR
EEV n°1
Auxiliary Regulation:
SUPERPAREMETERS
AC OR CHILLER WITH
BLDC COMPRESOR
Refrigerants EEV n°1
Main Refrigerant: R410A
SYSTEM CONFIGURATION
Auxiliary Refrigerant:
SAME AS MAIN REG.
Probes Value
EEV n°1
S1:
10.3barg
PROBES VALUE
S2:
12.6°C
S3:
10.3barg
S4:
12.8°C
EEV n°1
REGULATION
Superheat
Setpoint:
5.0K
EEV n°1
Valve Opening At
REGULATION
Start-Up:
58%
Pre-PositioningTime: 30s
EEV n°1
Stand-BY
REGULATION
Valve Opened: DISABLE
Valve Position:
0%
EEV n°1
PID
REGULATION
Prop.Gain:
5.0
Intedr.Time:
300.0s
Driv.Time:
0.0s
EEV n°1
Low SH Protection
REGULATION
Threshold:
1.5°C
Integral.Time:
10.0s
Alarm Delay:
2000s
En. Pump Manual: No
MANUAL MNG.
Ma01
Speed req.: 0%
Compr.Manual Control
Manual Mode:
No
MANUAL MNG.
Ma02
Speed Refer.:
0.0%
EEV N°1
MANUAL MNG.
Manual Positioning: No
Position: 0stp
EEV N°2
REGULATION
Manual Positioning: No
Position: 0stp
This drawing is the property of AQUA SOLANOR INC. It may not be used for any purpose other than the owner. AQUA
SOLANOR INC does not authorize the reproduction or conveyance of any information contained herein without prior written
Date
Scale
permission. This document is neither an engineering document, nor a construction document. Such documents shall be
produced in compliance with federal, provincial or municipal laws. The purpose of this document is to show the principle of
2022-09-23
NTS
operation of equipment.
2
3
3
4
EEV n°1
REGULATION
LOP Protection
Threshold:
-45.0°C
Integral Time:
10.0s
Alarm Delay:
120s
EEV n°1
MOP Protection
REGULATION
Threshold:
70.0°C
Integral Time:
2.0s
Alarm Delay:
120s
EEV n°1
ADVANCED
Power Supply
Mode:
24VDC
EEV n°1
ADVANCED
Min Opening Value
Min Steps:
70
EEV n°1
ALARMS CONFIGURATION
Low Suct.Temperature
Alarm Time out:
120s
EEV n°2
SUPERPAREMETERS
Valve: CAREL E2Vu
Main Regulation:
AC OR CHILLER WITH
BLDC COMPRESSOR
EEV n°2
Auxiliary Regulation:
SUPERPAREMETERS
AC OR CHILLER WITH
BLDC COMPRESOR
Refrigerants EEV n°2
Main Refrigerant: R410A
SYSTEM CONFIGURATION
Auxiliary Refrigerant:
SAME AS MAIN REG.
ALARMS CONFIGURATION
Probes Value
EEV n°2
S1:
10.3barg
PROBES VALUE
S2:
12.8°C
S3:
0.0barg
S4:
0.0°C
EEV n°2
REGULATION
Superheat
Setpoint:
30.0K
Fan High Speed: No
MANUAL MNG.
Ot07
Fan Low Speed: No
4 Way Valve: No
3 Way Valve: No
MANUAL MNG.
Ot08
Crank Heater: No
Chassis Heater: No
MANUAL MNG.
Ot09
Terminal Pump: No
Heater: No
Insert Inverter Set For
MANUAL MNG.
Ot10
Unmatch Compressor
No
4
5
6
EEV n°2
Valve Opening At
REGULATION
Start-Up:
30%
Pre-PositioningTime: 6s
EEV n°2
Stand-BY
REGULATION
Valve Opened: DISABLE
Valve Position:
0%
EEV n°2
PID
REGULATION
Prop.Gain:
3.0
Intedr.Time:
200.0s
Deriv.Time:
0.0s
EEV n°2
Low SH Protection
REGULATION
Threshold:
-1.0°C
Integral.Time:
2.0s
Alarm Delay:
2000s
EEV n°2
REGULATION
LOP Protection
Threshold:
10.0°C
Integral Time:
2.0s
Alarm Delay:
900s
EEV n°2
REGULATION
MOP Protection
Threshold:
65.0°C
Integral Time:
2.0s
Alarm Delay:
120s
EEV n°2
ADVANCED
Power Supply
Mode:
24VDC
EEV n°2
Low Suct.Temperature
Alarm Thresh.:
-50.0°C
Alarm Time out:
300s
2305 46th AVENUE, LACHINE (QC) H8T3C9
DWG.NO.:HSS306080CTRL
5
6
7
8
A
B
C
D
E
F
ANNEX_"C"_03
Revision
Sheet
0
3
7
8