Télécharger Imprimer la page

Carel Hydro Solar HSS030V2LS Manuel page 51

Publicité

Les langues disponibles

Les langues disponibles

Press Enter to switch
M05
BLDC Compressor
A
PROGRAM
B
PASSWORD
Press Enter to switch
M06
Power + Inverter
C
D
E
F
Ref. #
P/N
Designed by
Checked by
Approved by - date
File name
IAN
ROGER
2023-03-17
HSS306080CTRL
1
1
2
Compr.Timing
Minimum ON: 180s
Minimum OFF: 180s
COMPRESSOR REG.
Co01
Min.Time Between
2 Starts: 360s
High Press.Alarm
Dis.Press.Limit: 42.0bar
COMPRESSOR REG.
Co02
Dis.Press.Recover:40.0bar
Low Press.Alarm
Suc.Press.Cool.Limit:4.0bar
COMPRESSOR REG.
Co03
Suc.Press.Heat.Limit:0.5bar
Suc.Press.Heat.Limit:1.5bar
Low Press.Alarm
Start Delay: 180s
COMPRESSOR REG.
Co04
Run Delay: 30s
Start-Up Pressure Diferential
Control Max Presure Differ.
COMP_BLDC
Admitted: 3.0barg
Start-Up Pressure Diferential
Control
Equalization Mode:
COMP_BLDC
EEV PRE-OPENING
Max.Equaliz.Time:60s
EEV Opening: 80%
Defaut Settings
Motor Type :
POWER+
PARASONIC H240D5KZAAJ2
R410A
230V
Drive Type: PS2**252**
Write Defaults:
NO
Drive Type
Connected: 230V 25A
POWER+
Suggested: 230V 25A
Configuration
Data Comunic.Timeout:
POWER+
(090) 30s
AutoInstall Param.: NO
Output Frequency
POWER+
Minimum: (007) 30.0Hz
Maximum: (006) 220.0Hz
Skip Frequency 1
POWER+
Setpoint: (010) 0.0Hz
Band: (011) 0.0Hz
Skip Frequency 2
POWER+
Setpoint: (067) 0.0Hz
Band: (068) 0.0Hz
Skip Frequency 3
Setpoint: (069) 0.0Hz
POWER+
Band: (070) 0.0Hz
Skip Frequency
Nominal: (024) 6.0Hz
POWER+
Derating: (025) DISABLED
PTC Alarm
Enabling: (027) NO
POWER+
Delay: (028)
0s
Reverse Speed:
(008)
DISABLED
POWER+
Speed Derating Mode:
(009)
NONE
Stop Mode:
(033)
---
POWER+
Flying Restart::
(034)
DISABLED
Relay Configuratio:
POWER+
(026)
ALARM
Poles Numbers:
Motor Control Mode:
POWER+
(000)
PM MOTOR
This drawing is the property of AQUA SOLANOR INC. It may not be used for any purpose other than the owner. AQUA
SOLANOR INC does not authorize the reproduction or conveyance of any information contained herein without prior written
Date
Scale
permission. This document is neither an engineering document, nor a construction document. Such documents shall be
produced in compliance with federal, provincial or municipal laws. The purpose of this document is to show the principle of
2022-09-23
NTS
operation of equipment.
2
3
3
4
Start-Up Failure Control
Pressure Difference
COMP_BLDC
Min.Variation: 0.2barg
Control Period: 45s
Start-Up Failure Control
Restart Delay: 30s
COMP_BLDC
Max Retry Number: 5
Speed Mnagemetn
Start-UP Forced Speed:
Cool/Het: 50.0rps
COMP_BLDC
Hotwater: 40.0rps
Max Speed: 80.0rps
Min Speed: 30.0rps
Speed Mnagemetn. rps/s
Deceleration Rate: 1.0
COMP_BLDC
Acceleration Rate: 1.0
Switch-OFF Rate: 1.0
Evelope Control
Speed Reduction Rate:
0.5rps/s
COMP_BLDC
Min Speed Admitted:
40.0rps
Motor Base Frequency:
(001)
200.0Hz
POWER+
Motor Base Voltage:
(002)
242Vrms
Motor Rated Current:
(003)
25.0Arms
POWER+
Motor Power Factor:
(004)
100
Out Current Maximum:
(005)
100.0%
Speed Profile
Freq.1 (012):
18.0Hz
POWER+
Freq.2 (013):
------Hz
Freq.3 (014):
------Hz
Speed Profile
Acc.1 (015):
18.0Hz/s
Acc.2 (016):
2.0Hz/s
POWER+
Acc.3 (017):
2.0Hz/s
Acc.4 (018):
2.0Hz/s
Speed Profile
Delay (019):
-s
POWER+
Delay (020):
-s
Delay (021):
-s
Speed Profile
Delay Execution:
(022.0)
------
POWER+
Force Freq. 2:
(022.1)
------
Speed Profile
Deceleration Ramp:
POWER+
(023)
2.0Hz/s
V/F Boost Voltage:
(035)
0.0%
V/F Freq.Adjustment:
POWER+
(036)
0.0%
V/F Volt.Adjustment:
(037)
0.0%
Motor Magn.Current:
(045)
0.0A
Stator Resistance:
POWER+
(046)
830mohm
Roto Resistance:
(047)
0mohm
4
4
5
6
Evelope Control
Out Of Envelope Alarm
COMP_BLDC
Timeout: 360s
LDC RETRY SETTINGS
Low Pressure Diff. Alarm
Timeout: 360s
COMP_BLDC
Evelope Control
Low Ratio Management
COMP_BLDC
By Compre.Speed Up: YES
Discharge Gas Control
Hogh Discharge Temp.
COMP_BLDC
Limit: 110.0°C
Alarm: 115.0°C
Speed Control Due To
Discharge Gas
Action Distance 20.0°C
COMP_BLDC
Action Pause: 90s
Compressor Speed
Reduction: 3.0%
Restries Number: 3
LDC RETRY SETTINGS
Control Time Retries: 60m
Stator/LD Inductance:
(048)
3.5mH
POWER+
Leakage Factor:
(049)
0
Lq Inductance:
(050)
6.4mH
Speed Loop Kp:
(055)
75.0%
POWER+
Speed Loop Ti:
(056)
100msec
Magnetizing Time:
(051)
100msec
POWER+
Starting Current:
(057)
40.0%
10.0A
Freq.For Start Curr.:
(058)
20.0%
Crankcase Heater Mode:
(100.2)
AUTO
Crankcase Current:
POWER+
(065)
0.0%
0.0A
STO Alarm Management.:
(066)
MAN.RESET
Phase Loss Detection:
POWER+
(076.0)
ENABLE
Overload At Power-On:
POWER+
(076.3) RESET
Inductance Saturation
Reduction:
POWER+
(077)
10.0%
2.5A
Save Custom Data
Save To CUSTOM:
NO
POWER+
Inverter Online
Retries Setting
Retries Number: 3
POWER+
Control Time Retries:
60m
2305 46th AVENUE, LACHINE (QC) H8T3C9
5
6
7
8
Envelope Alarms:
R
A
M :Manual
R :Semiaut
Information
FB Version: 2.0. 62
Unit Mode: User
User Mode: Multiple
Test Mode EVI Opening
Condition Able
TEST SENSOR Able
B
C
Motor Control Alarms
Alarms 01-08:
POWER+
A A A A A A A A
Alarms 09-16:
A A A A A A A A
M :Manual
A :Semiaut
Motor Control Alarms
Alarms 17-24:
A A A A A A A A
POWER+
Alarms 25-28
98
99 :
A A A A
A
A
M :Manual A :Semiaut
USafety Control Alarms
Alarms 01-08:
A A A A A A A A
POWER+
Alarms 09-16:
A A A A A A A A
D
M :Manual A :Semiaut
USafety Control Alarms
Alarms 17-24:
A A A A A A A A
POWER+
Alarms 25-32:
A A A A A A A A
M :Manual A :Semiaut
Information
Fb Version: 2.0. 62
Boot Release: 192
FW Release: 151
POWER+
FW Checksum: 832
MC Release:
0
Hardware ID: 2025
E
F
ANNEX_"C"_02
Revision
Sheet
DWG.NO.:HSS306080CTRL
0
2
7
8

Publicité