Press Enter to switch
M01
Unit On/Off
A
Press Enter to switch
M02
I/O Mask
B
C
Press Enter to switch
M03
Time Zone/Clock
D
Press Enter to switch
M04
User Mask
E
F
Ref. #
P/N
Designed by
Checked by
Approved by - date
File name
IAN
ROGER
2023-03-17
HSS306080CTRL
1
1
2
UNIT ON/OFF
B1: Inlet Temp. -999.9°C
INPUT/OUTPUT
Sn01
B2:Outlet Temp.-999.9°C
B3: Ext Temp.
12.9°C
B4: Disch.Gas 12.5°C
INPUT/OUTPUT
Sn02
B5:Suct. GasTemp 12.5°C
B6: Disch.Press 10.3bar
B7: Suct.press 10.3bar
INPUT/OUTPUT
Sn03
B8:HotwaterTemp 12.8°C
B9: Coil Temp. 12.3°C
Digit Input Status
ID1: Floe Switch
INPUT/OUTPUT
Sn05
ID2: Linkage Switch
ID3: A/C Linkage Switch
Digit Input Status
ID4: Cooling Linkage
INPUT/OUTPUT
Sn06
ID5: Phase.Switch
ID6: Heating Linkage.
Digit Input Status
D01: Fan High Speed
INPUT/OUTPUT
Sn07
D02: Fan Low Speed
D03: 4 Way Valve.
Digit Input Status
D04: Pump
INPUT/OUTPUT
Sn08
D05: Chassis Heater
D06: Crank Heater
Date: 15/03/23
DATE/TIME CHANGE
C101
Hour: 00:00
Day: Wednesday
Timezone On/Off:
CLOCK MNG.
C102
Disable
Timezone Setpoint:
Disable
Work Mode Select:
UNIT MODE
U00
Heating
Heating Setp.: 45.0°C
SETPOINT
U01
Cooling Setp.: 12.0°C
Hotwater Setp.: 50.0°C
Hot Water Setp.
Temp.Diff.; 5.0°C
SETPOINT
U02
Stop Temp.Diff.: 0.0°C
Cool And Heat Mode
SETPOINT
U03
Temp.Diff.; 5.0°C
Stop Temp.Diff.: 2.0°C
PID Management
SETPOINT
U04
Kp:
5.0°C
Integral: 200s
Differential: 0s
Pump Work; Normal
PUMP CONTROL
U05
Pump Auto: ENABLE
Fan Mode: Daytime
Enable Heater: ALL
USER CONFIGURE
U06
Enable Chassis/Crack
Heater: Enable
Comp.Delay: 50min
USER CONFIGURE
U07
ExT.Temp.Setp.: -15.0°C
This drawing is the property of AQUA SOLANOR INC. It may not be used for any purpose other than the owner. AQUA
SOLANOR INC does not authorize the reproduction or conveyance of any information contained herein without prior written
Date
Scale
permission. This document is neither an engineering document, nor a construction document. Such documents shall be
produced in compliance with federal, provincial or municipal laws. The purpose of this document is to show the principle of
2022-09-23
NTS
operation of equipment.
2
3
3
4
Digit Input Status
D07: Three Valve
INPUT/OUTPUT
Sn09
D08: Terminal Pump
D09: Heater
Analog.Output Status
Y1: Fan Output 0.0%
INPUT/OUTPUT
Sn10
Y3: Pump Output 0%
Analog.Output Status
INPUT/OUTPUT
Sn11
DC Fan 1 Output 0rpm
DC Fan 1 Feedback 0rpm
Analog.Output Status
INPUT/OUTPUT
Sn12
DC Fan 2 Output 0rpm
DC Fan 2 Feedback 0rpm
Compre.Capacity Regul.
Required Cap.: 0.0%
Comp_BLDC
Actual Cap.: 0.0%
Actual Speed: 0.0rps
Envelope Data
Cond.Press.: 10.3barg
Evap.Press.: 10.3barg
Comp_BLDC
Envelope Status:
Low Press.Differential
Alarm Countdown: 360s
Envelope Data
Press.Diff.: -0.1barg
Comp_BLDC
Press.Radio: 1.0
Low PD Countdown: 360s
PUMP CONTROL
U08
Delta Temp.Set: 5.0°C
USER CONFIGURE
U09
Auto Start: Enable
Enable
Switch: Disable
AMBTEMP SWITCH
U10
AmbTemp Switch Setp:
20.0°C
Amb Temp.Diff: 4.0°C
ANTILEGIONELLA SET
Set Compensation
Disable
AmbTemp
Setp.
X1: -10.0°C
Y1: 45.0°C
ECO. MODE-HEAT
U12
X2:
0.0°C
Y2: 40.0°C
X3: 10.0°C
Y3: 35.0°C
X4: 20.0°C
Y4: 30.0°C
Set Compensation
Disable
AmbTemp
Setp.
X1: 0.0°C
Y1: 50.0°C
ECO. MODE-HOTWATER
U13
X2:10.0°C
Y2: 50.0°C
X3:20.0°C
Y3: 45.0°C
X4:30.0°C
Y4: 45.0°C
4
5
6
Cooling Cpacity:
0%
T
12.5°C
P
Evd 1COMPRESSOR
12.5°C
T
P
10.3barg 11.5°C
0stp
0.0%
Dish.SH
1.2K
Evd 1 CIRCUIT
Status:
Off
Protection:
None
Suction SH: 1.0K
Cooling Cpacity:
0%
12.5°C
T
P
Evd 2COMPRESSOR
12.5°C
T
10.3barg 11.5°C
P
0stp
0.0%
Evd 2 CIRCUIT
Status:
Off
Protection:
None
Suction SH: 1.2K
Status
Drive Status: (104)
Drive Temperature:(114)
Power+
13.0°C
Alarm Code (105):
0: No Fault
Speed Reference:
(102) 30.0Hz
Power+
Rotor Speed;
(132) 0.0Hz 0rpm
Set Compensation
Disable
AmbTemp
Setp.
MODE-COOL
X1: 20.0°C
Y1: 15.0°C
X2: 25.0°C
Y2: 15.0°C
X3: 30.0°C
Y3: 12.0°C
X4: 35.0°C
Y4: 12.0°C
Enable Antileg.:
NO
Temp. Setp>:
65.0°C
Timer:
MON
08:00-11:00
2305 46th AVENUE, LACHINE (QC) H8T3C9
5
6
7
8
A
Motor
Current:(109) 0.0Arms
Power+
Voltage: (111) 0Vrms
Power: (110) 0.00KW
DC Bis
Voltage: (113) 287Vdc
Power+
Ripple: (134) oVdc
Frequencies
B
Operating Switc.Freq:
Power+
(123) 6kHz
Pre-ramp Setpoint:
(125) 0.0Hz
Registers
Status:(106)
N
Power+
Speed:(107)
N
Overload Accumulator
Motor: (153) 0.0%
Power+
Drive: (154) 0.0%
C
D
E
F
ANNEX_"C"_01
Revision
Sheet
DWG.NO.:HSS306080CTRL
0
1
7
8

Publicité

loading

Ce manuel est également adapté pour:

Hydro solar hss060v2lsHydro solar hss080v2ls