GB
5.5 Filling
1. Undo the flap lid cam by pulling apart the fasten-
ing lugs on the locking side, and fully open the
flap lid.
2. Open delivery line ball valve c.
3. Remove the hose and delivery nozzle from the
integrated holder and insert the delivery spout
fully into the tank/container to be filled.
4. Operate or open the delivery nozzle.
5. Move the hand pump lever forwards and
backwards in a horizontal direction and start
the filling procedure.
Operate the hand pump only when the ball
valve and delivery nozzle are open!
Tank ventilation and pressure relief are performed
automatically by the integrated valve a.
i
Important!
Constantly monitor the filling process.
6. Close delivery nozzle f and allow it to
stop dripping.
7. Place hose and delivery nozzle into the
integrated holder.
8. Close delivery line ball valve c.
9. Close the flap lid until it clicks audibly into place.
6. Accessories
The following accessories are available for the
DT-Mobil Easy:
6.1 Flap lid
• Lockable protection to prevent unintentional
opening of fittings: Order code 10214
16
All manuals and user guides at all-guides.com
7. Maintenance and inspection
7.1 Safety measures
i
Important!
The operator must provide any protective
clothing that may be required.
Who can carry out maintenance
and inspection work?
Normal maintenance work may be
carried out by operational personnel.
i
Important!
Inspections of the filling stations with
ADR approval may only be performed
by specially trained personnel.
Ask the manufacturer about these training courses.
7.2 Maintenance and inspection table
Interval
Assembly
As
Outside of
required
filling station
Monthly
Container
Monthly
Piping
system
Annually
Tank
(suction
filter)
Every
Filling
2.5 years
station
1. Unscrew the lid from
the filling opening
2. Reach into the
opening and pull out
the suction hose
3. Clean the filter
4. Perform steps 1-3
in the reverse
sequence.
Action
Clean off any stuck-on
dirt or diesel
Visual check for damage
Check hoses for cracks
and porosity,
check fittings for leaks
(replace defective parts)
Clean (see picture) with
a low level of diesel fuel
in the tank
Inspection by
experts with:
- Documentation in the
test protocol (see 10)
- Entry on type plate
with waterproof marker
3
2
1
Fig. 7.2: Suction filter

Publicité