32
en | Safety instructions
Notice!
Video-based fire detection sets camera settings to a specific
i
preset.
Setting of the image parameters can be changed only to a
limited extent.
Notice!
i
Respect data protection.
The relevant data protection and privacy rules are to be
complied with.
Notice!
Minimum Illumination required.
i
To ensure the proper functioning of the video-based fire
detection algorithm, a minimal illumination of 1 lx is required.
If the illumination is less than 1 lx, the internal IR illumination
is to be activated in the camera menu.
Notice!
No detection of moving fire.
i
Moving fires might not be detected by the video-based fire
detection. An example of a moving fire is a fire on a moving
conveyor belt.
Notice!
i
Avoid obstructions in the field of view!
Covered fires cannot be detected correctly. An unobstructed
view of the detection area is necessary.
Notice!
i
Optimized smoke detection.
The video-based fire detection algorithm is optimized for
smoke of smoldering fires.