Télécharger Imprimer la page

Samsung DV53BB8900 Serie Mode D'emploi page 19

Publicité

Les langues disponibles

Les langues disponibles

Ducting requirements (Not applicable to ventless (heat pump) models)
Weather hood type
No. of 90° elbows
0
1
2
3
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer's vent system with an existing exhaust system:
• Make sure the exhaust system meets all applicable local, state, and national regulations.
• Verify you are not using a flexible plastic duct.
• Make sure to check for and remove all lint buildup from inside the existing ducts.
• Confirm the duct is not kinked or crushed.
• Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column or be less than 0.
Note that these values are measured with the dryer running with a manometer presented to the exhaust
duct that connects to the dryer. The dryer's drum must be empty and the lint filter must be clean.
DV8900HB_SimpleUX_WEB_OID57652_01_English.indd 19
DV8900HB_SimpleUX_WEB_OID57652_01_English.indd 19
Recommended
4" (10.2 cm)
Rigid
80 ft. (24.4 m)
68 ft. (20.7 m)
57 ft. (17.4 m)
47 ft. (14.3 m)
Use only for short-run
installation
2.5" (6.4 cm)
Rigid
74 ft. (22.6 m)
62 ft. (18.9 m)
51 ft. (15.5 m)
41 ft. (12.5 m)
English 19
2023/6/29 15:27:55
2023/6/29 15:27:55

Publicité

loading

Ce manuel est également adapté pour:

Dv53bb8900hda2