Remarks:
- Dipswitches ds8,ds7 ,ds6 ,ds2 and ds1 are not assigned and should remain off.
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 5.
- These settings are not relevant for slaves. They are however relevant for followers. If
you don't want to bother about an Inverter being a master/slave/follower then the
easiest and most straight forward way is to set all settings identically on all Inverters.
5.5.1 AES (Automatic Economy Switch)
Procedure: set ds5 to the required value:
ds5
off = AES off
on = AES on
Note: The AES option is only effective if the unit is used 'stand alone'.
5.5.2 Inverter voltage
Procedure: set ds4 to the required value:
ds4
off = 240V
on = 230V
5.5.3 Inverter frequency
Procedure: set ds3 to the required value:
ds3
off = 60Hz
on = 50Hz
5.5.4. Important note on ds2 and ds1
If the last 3 digits of the Multi firmware is in the 100 range (so the firmware
number is xxxx1xx (with x any numer)) then ds1 & ds2 are used to set a
Multi in stand-alone, parallel or three-phase. Please consult the appropriate
manual.