Télécharger Imprimer la page

Lenze E94AYCCA Instructions De Montage page 41

Publicité

Les langues disponibles
  • FR

Les langues disponibles

All manuals and user guides at all-guides.com
2. Please check the compliance with the segment cable length in Tab. 2.
The segment cable length is specified by the cable cross−section and the number of nodes.
Without a repeater, the segment cable length corresponds to the total cable length.
Cable cross−section
Max. number of
nodes per
0.25 mm
segment
2
240 m
5
230 m
10
230 m
20
210 m
32
200 m
63
170 m
100
150 m
Tab. 2
Segment cable length
3. Compare both values.
If the value given in Tab. 2 is smaller than the total cable length given in Tab. 1, repeaters
must be used. Repeaters divide the total cable length into segments.
Example: Selection help
Given:
l
Cable cross−section:
l
Number of nodes:
l
Repeater:
At maximum number of nodes (128), the following cable lengths/number of repeaters
must comply with:
Baud rate [kbit/s]
Max. cable length [m]
Segment cable length [m]
Number of repeaters
EDK94AYCCA DE/EN/FR/ES/IT 3.0
2
2
0.5 mm
430 m
420 m
410 m
390 m
360 m
310 m
270 m
(according to cable specification ^ 39)
2
0.5 mm
128
Lenze repeater, type 2176 (cable reduction: 30 m)
10
20
50
8000
3900
1500
270
270
270
33
16
6
l
Electrical installation
Wiring the CAN bus
2
0.75 mm
650 m
640 m
620 m
580 m
550 m
470 m
410 m
125
250
500
630
290
110
270
270
110
2
1
6
2
1.0 mm
940 m
920 m
900 m
850 m
800 m
690 m
600 m
800
1000
40
17
40
17
41

Publicité

loading