8 Settings
Before the first set-up the basic teach empty state must be carried out�
8.1 Carry out the basic teach empty state
The basic teach empty state sets the unit to the empty tank and the installation
conditions (e�g� the set installation length)� Previous settings are deleted�
► Empty the tank until the medium is at least 20 mm below the end of the probe�
► Press [OUT OFF], keep it pressed for min� 2 s / max� 6 s�
> The yellow LED flashes slowly� When the button is released, it goes out�
The unit is then ready for operation and set as NO unit (output ON when the
level has been reached)�
If the unit is to be set as NC unit:
► After emptying the tank press [OUT ON] instead of [OUT OFF]� After releasing
the pushbutton, the yellow LED lights continuously�
8.2 Carry out the basic teach full state
The empty adjustment is sufficient for media with a low dielectric constant (e�g�
oils)� For aqueous media the sensitivity must be optimised by a full adjustment�
The full adjustment does not change the settings of the empty adjustment�
► Fill the tank until the active zone of the unit is covered�
> If the unit is set as NO unit (→ 8.1), the yellow LED lights, if it is set as NC unit,
it goes out�
► If the unit is set as NO unit: press [OUT ON] and keep it pressed for at least
6 s�
> The yellow LED flashes slowly, after 6 s it flashes quickly� After releasing the
pushbutton, it lights continuously�
If the unit is set as NC unit: After filling the tank press [OUT OFF] instead of
[OUT ON]� After releasing the pushbutton, the yellow LED goes out�