Télécharger Imprimer la page

Toshiba Carrier MMY-MAP0726HT6P-UL Manuel Du Propriétaire page 9

Publicité

Les langues disponibles

Les langues disponibles

6
Installation
Ask the installation company about important points of general instruction.
Location
• Avoid installing near machines emitting high frequency waves.
• Not suitable for chemical plants such as liquefi ed carbon dioxide refrigerant plants.
• Avoid places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the
interior of the air conditioner, it may spontaneously combust and start a fi re.
• A failure may occur in certain locations such as the following:
• Areas with large amount of oil droplets (including machine oil) or vapors
• Salty areas near oceans, etc.
• Hot springs emitting sulfi dizing gas.
• Heavily acidic or alkaline places.
Special maintenance or parts are required for use in the above places. For details, contact the dealer where you
purchased the product.
• Leave an enough space around the air intake and outlet of the outdoor unit so that the ventilation is not
restricted.
• Avoid places where strong wind may blow against the air intake and discharge of the outdoor unit.
• Attach a snow stand, snow hood, etc. to the outdoor unit for use in snowfall areas. For details, contact the
dealer where you purchased the product.
• Make drain water from the outdoor unit is emitted into places with good drainage.
• Attach the air fi lter to the indoor unit. If not, dust may accumulate on the heat exchanger or other parts in the air
conditioner and cause a water leak.
• Keep a distance of at least 3.3ft (1m) between the air conditioner/remote control and a TV or radio. Failure to
observe this precaution may cause visual disturbance or noise.
• Leave a distance of at least 4.9ft (1.5 m) between the air discharge and a fi re alarm. If this precaution is not
observed, the alarm may not work properly or detect fi re in case of fi re.
Be careful of operation sounds
• Locate the unit in a place secure enough so that the sounds and vibrations do not increase.
• If something is placed near the air discharge of the outdoor unit, noise may increase.
• Do not disturb neighbors with cool/warm air or noise coming from the air discharge of the outdoor unit.
15-EN
1117907101 EN FR.indb 8
1117907101 EN FR.indb 8
7
Air conditioner operations
Check before operation
• Turn on the power switch at least 12 hours before
starting operation.
• Connect the ground wire securely.
• Attach the air fi lter to the indoor unit.
Heating performance
• A heat pump system, which gathers outside heat
and emits it into a room, is used for heating. When
the outside air temperature falls, the heating
capacity of the unit is reduced.
• When the outside temperature is low, it is
recommended that other heating equipment is used.
Defrosting during heating
• If frost falls on the outdoor unit during heating,
defrosting is automatically performed (for
approximately 2 - 10 minutes) to increase the
heating effect.
• The fan of the indoor unit is stopped during
defrosting.
3-minute protection
The outdoor unit will not operate for approximately 3
minutes after the air conditioner has been immediately
restarted after stopping, or the power switch has been
turned on. This is to protect the system.
Auto restart
The unit will stop after a power failure.
• The unit will restart automatically in the same
operating mode as before the power failure when
the power is restored.
– 8 –
Fan rotation of a stopped
indoor unit
• While other indoor units operate, the fans on indoor
units in stand-by mode rotate for several minutes
approximately once per one hour to protect the
machines.
Protective device
(High pressure switch)
The high pressure switch stops the air conditioner
automatically when excessive load is applied to the air
conditioner.
If the protective device activates, the unit's running
stops and the operation lamp blinks.
When the protective device activates, the
indicator
and the check code are displayed on the remote
control.
The protective device may activate in the following
cases:
During cooling
• When the air intake or air discharge of the outdoor
unit is blocked.
• When strong wind blows continuously against the air
discharge of the outdoor unit.
During heating
• When dust or dirt is excessively adhered to the air
fi lter of the indoor unit.
• When the air discharge of the indoor unit is blocked.
NOTE
When the protective device activates, turn off the
power switch, remove the cause, and then restart
running.
3/21/16 11:44 AM
3/21/16 11:44 AM
EN
EN
EN
ES
16-EN

Publicité

loading