Télécharger Imprimer la page

Autosen AD006 Notice D'utilisation page 21

Module io-link

Publicité

Les langues disponibles

Les langues disponibles

4.5.4 Combination of different input filters
The different input filters can be combined� In the following example all 3 filters are
used:
Digital input
Debounce filter
output
Filter hold output
Inverter output
IO-Link
process data
1: Cycle time
5 Installation
► Disconnect power before installation�
► For installation choose a flat mounting surface�
► Fasten the module onto the mounting surface using M5 screws and washers�
Tightening torque 1�8 Nm�
► Connect the plugs of the sensors to the M12 sockets�
Tightening torque max� 1 Nm�
► Cover unused sockets with protective caps�
Tightening torque 0�6���0�8 Nm�
Observe the maximum tightening torque of the connection cables�
UK
21

Publicité

loading

Ce manuel est également adapté pour:

Ad007