4.5 Digital input filters
The input signals can be changed via different filters before they are transmitted
via IO-Link� The following filters are available and are applied to the input signal in
this order:
1� Debounce
2� Hold
3� Invert
Each of these filters can be configured separately via IO-Link� More information is
available in the IODD at www�autosen�com�
The unit detects signals of a length of min� 1�5 ms� Shorter signals are not de-
tected�
Periodic signals are only detected reliably if the signal period is at least
twice as long as the cycle time�
The precision of the digital input filters is ± 1 ms�