Autosen AD006 Notice D'utilisation page 17

Module io-link

Publicité

Les langues disponibles

Les langues disponibles

3.1.2 Device-specific information
You will find the IODDs necessary for the configuration of the IO-Link unit and
detailed information about process data structure, diagnostic information and
parameter addresses at www�autosen�com�
3.1.3 Parameter setting tools
You will find all necessary information about the required IO-Link hardware and
software at www�autosen�com�
4 Function
After power on, the unit is in the RUN mode (normal operating mode)�
4.1 Visual indication
The unit
- indicates the current physical state of the inputs (yellow LED DI1/DI2)
- signals a correct operation (green LED US on, red LED L/R off, red LED INT
off)
- signals a short circuit of min� one sensor supply on the left side (red LED L
on) and on the right side (red LED R on)
- signals an internal fault (red LED INT on)
4.2 Parameter setting
Device-specific parameter lists for IO-Link parameter setting are available at www�
autosen�com�
4.3 Digital inputs
The unit AD006 has 6x2 digital inputs�
The unit AD007 has 10x2 digital inputs�
4.4 Sensor supply
The unit AD006 has 6 sensor supplies� The unit AD007 has 10 sensor supplies�
Every sensor supply is limited to 100 mA� For the unit AD006 the total current is
max� 700 mA; for the units AD007 max� 1100 mA� Every sensor supply has its own
short-circuit monitoring� The output voltage of the sensor supplies is proportional
to the operating voltage which can vary within the IO-Link specification (18���30 V
DC)�