Télécharger Imprimer la page

Bosch FNM-420-A-RD Guide D'installation page 8

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 10
8
en | Safety instructions
1
Safety instructions
Notice!
Installation must only be carried out by authorized specialist
personnel.
Only if the sounder volume is set to the maximum level, the
i
certified sounds (no. 1, 8, 10, 24) comply with EN 54-3.
Certified sound measurements are listed in
Bulletin_Sound_Pressure_Level_EN54-3.pdf (F.01U.344.055 for
FNM-420-A, F.01U.344.056 for FNM-420-B), which can be
obtained from the manufacturer.
Notice!
i
Electrostatic discharge (ESD)! Electronic components could be
damaged. Ground yourself using a wrist strap or take other
suitable actions.
2
Functional description
The volume of each 32 tone variants (incl. DIN tone 33404 part
3) has up to 5 levels and can be adjusted according to the
operational environment. The sound level varies between 65 dB
and 102 dB depending on the tone type and volume.
3
Technical specifications
See Installation, page 4 .
2023-07 | 06 | F.01U.099.623
Bosch Sicherheitssysteme GmbH
Sounder

Publicité

loading

Ce manuel est également adapté pour:

Fnm-420-a-whFnm-420-b-rd