Problem
The charger is not
functioning
The battery is not
being charged fully.
The battery is
overcharged.
Battery charge
current drops to 0
when the absorption
voltage is reached
24
Cause
The AC input voltage or frequency
is out of range.
The thermal circuit breaker has
tripped.
Incorrect charging current.
A defective battery connection.
The absorption voltage has been
set to an incorrect value.
The float voltage has been set to
an incorrect value.
The internal DC fuse is defective.
The absorption voltage has been
set to an incorrect value.
The float voltage has been set to
an incorrect value.
A defective battery.
The battery is too small.
The battery is too hot.
Alt. 1: Battery overtemperature
(> 50°C)
Alt 2: Battery temperature sensor
faulty
Solution
Ensure that the input voltage is
between 185 Vac and 265 Vac,
and that the frequency matches
the setting.
Reset the 16 A thermal circuit
breaker.
Set the charging current at
between 0.1 and 0.2x battery
capacity.
Check the battery terminals.
Adjust the absorption voltage to
the correct value.
Adjust the float voltage to the
correct value.
Inverter is damaged.
Adjust the absorption voltage to
the correct value.
Adjust the float voltage to the
correct value.
Replace the battery.
Reduce the charging current or
use a battery with a higher
capacity.
Connect a temperature sensor.
- Allow battery to cool down
- Place battery in a cool
environment
- Check for shorted cells
Unplug battery temperature
sensor from the MultiPlus.
Reset the MultiPlus by switching
it off, then wait for 4 seconds and
switch it on again
If the MultiPlus now charges
normally, the battery temperature
sensor is faulty and needs to be
replaced