Terminal block
113(Y),114(M)
115(Y),116(M)
117(G),118(G0)
119(Y),120(M)
121(G),122(G0)
123(Y),124(M)
125, 126
127, 128
129(Y),130(M)
131, 132
1) A 1-phase pump with integrated oveload protection can be powered by a jump wire from terminal block L to function terminal.
2) Control voltage for duct-mounted EQKK electrical heaters: Connect a circular coil directly to terminal block relay function.
For rectangular coils jump wire power from L through function terminal block. Connect to coil on N and output from functional terminal block.
3) Factory installed EQEK electrical heater. Control voltage 24VAC is jump wired through the functions potential-free relay.
Note: G0 and M are internally connected
11
Fläkt Woods
All manuals and user guides at all-guides.com
Type
Basic function
Universal I/O X13
Pre-heater control signal
Universal I/O X14
Humidity sensor in supply
air
24VAC
Power supply 24VAC
Analogue output
Outdoor damper control
Y11
signal
24VAC
Power supply 24 VAC
Active mixing control signal
Analogue output
Y12
Mixing damper control
Universal I/O X15
signal
Universal I/O X16
Fire alarm
Universal I/O X17
Rotor signal
Universal I/O X18
Rotor alarm
9397 UN 2015.09.10
Further information
0...10 VDC for valve actuator or electrical heater, pre-heater
0...10 VDC from humidity sensor in supply air
24 VAC for humidity sensor in supply air
0...10 VDC for outdoor damper actuator, ST5
Power supply 24 VAC to extract damper actuator, ST2,
for active mixing
Control signal 0...10 VDC to extract damper actuator, ST2,
for active mixing
0...10 VDC for mixing damper actuator, ST3
Signal from potential-free relay in external fire alarm. NC
2
Higher prio than Fire alarm
0...10 VDC for rotor speed
Alarm from rotor when digital signal is used
54
1
.
The document was orginally written in Swedish.
Subject to changes.