Installation Instructions for Ground Lug Kit
SAFETY INSTRUCTIONS
Note: This instruction outlines recommended
installation procedure.
1. Turn OFF and lock out the power supplying the Safety
Switch.
2. Turn the Safety Switch OFF.
Ground Lug Kit HG61234
Fig. 1
©
2000 Siemens Energy & Automation, Inc.
All manuals and user guides at all-guides.com
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power
supplying this Safety Switch
before installing kit.
Replace the covers and shields
before restoring power to switch.
Ground Lug Kit,
Item:
Catalog No. HG61234 & HG656
For use with:
30-600 Amp
VBII Safety Switches
1
2
Page
of
500202A02
Pc. No.
3. HG656 Kit Only: If mounting Ground Lug to a painted
surface, remove and discard protective plate and pro-
tective plate mounting screw to expose metal, see
Fig. 2.
4. Position Ground Assembly over existing hole as shown
in Fig. 1 for HG61234 or Fig. 2 for HG656.
5. Insert green thread rolling screw in mounting hole and
torque to 29 lb.-ins. for Kit HG61234 or 64 lb.-ins. for
Kit HG656.
6. Close cover before supplying power to this switch.
Ground Lug
Wd—g–†Ábg‰
Mounting Screw
c—g–f‘–‰Ái…d‡i
Line Base Assembly
Ground Lug Kit HG656
Fig. 2
Ground Lug
Wd—g–†Ábg‰
Protective Plate
fd—f‡…f‘h‡Áf”ƒf‡
(Enclosure with
'U–…”—egd‡Ái‘f
Painted Mounting
fƒ‘–f‡†Ác—g–f‘–‰Á
igdˆƒ…‡Áe–”k(
Surface Only)
Plate Mounting Screw
f”ƒf‡Ác—g–f‘–‰Ái…d‡i
(Enclosure with Painted
'U–…”—egd‡Ái‘fÁfƒ‘–f‡†
Mounting Surface Only)
c—g–f‘–‰Áigdˆƒ…‡Áe–”k(
b‘–‡Ái‘‡”†
Line Shield
b‘–‡ÁRƒe‡ÁQee‡•„”k

Publicité

loading

Sommaire des Matières pour Siemens HG61234

  • Page 1 Safety Switch before installing kit. 5. Insert green thread rolling screw in mounting hole and Replace the covers and shields torque to 29 lb.-ins. for Kit HG61234 or 64 lb.-ins. for before restoring power to switch. Kit HG656. SAFETY INSTRUCTIONS 6.
  • Page 2 4. Inserer la vis verte à rouler les filets dans le trou de hors tension et l'isoler du secteur avant d'installer le jeu. montage et la serrer à 29 lb-po (jeu HG61234) ou 64 Remettre le couvercle et le lb-po (jeu HG656).

Ce manuel est également adapté pour:

Hg656