GE SA-DACT Fiche D'installation page 2

Publicité

Les langues disponibles

Les langues disponibles

SA-DACT wiring
The dialer phone lines connect to connectors on the dialer's main
circuit board. Phone line 1 connects to connector J1 and phone
line 2 connects to connector J4.
The card typically connects to an RJ-31X block using an 8-
position, 4-conductor modular cord. Wire the RJ-31X block as
shown below.
Note:
Install a listed secondary telephone protector between the
telco network and the SA-DACT card. The SA-DACT card must be
the next piece of equipment that connects to the telephone
company (TELCO) telephone lines.
SA-DACT wiring
TELCO
Line 2
TELCO
Line 1
Telephone protector
4
5
3
6
2
7
1
8
RJ-31X block
(supplied by installer)
LINE 2
J4
J1
2 of 8
Protected premises
punch down block
Tip
Ring
Tip
Ring
Telephone protector
4
5
3
6
2
7
1
8
8-position, 4-conductor
modular cords
(supplied by installer)
LINE 1
SA-DACT testing
A dialer test is a test of the telephone line for each dialer account.
When a dialer is tested, a normal or abnormal test message
(depending on the state of the system) is sent to the selected
account. If the dialer is set up for dual line operation, a test
message is sent to both lines regardless of the success of the
transmission for either account.
Note:
Before conducting a test, configure the dialer's accounts for
proper operation.
To conduct a dialer test:
1.
Press the control panel's Menu button.
2.
Choose Test.
3.
Choose Dialer.
4.
Select the account that you want to test.
Tip
Ring
5.
Press Enter.
Note:
The test message is sent to the CMS account that you
selected. For verification of the CMS account receiving the
PBX
test message, you must be in contact with the CMS account
during the test. Nothing is displayed on the LCD display.
Tip
6.
Press Cancel to return to the previous menu.
Ring
– or –
Press the Menu button to exit menu mode.
SA-DACT specifications
Phone line type
Phone line connector
Communication formats
Operating voltage
Operating current
FCC registration number
Industry Canada
Registration number
Ringer equivalence number
Operating environment
Temperature
Humidity
One or two loop-start lines on a public,
switched network
RJ-31/38X (C31/38X)
Contact ID (SIA DC-05)
24 VDC
Standby/Alarm: 41 mA
Max.: 100 mA
GESAL01BSADACT
3944A-SADACT
0.1B
32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at 90°F (32°C)
P/N 3101099 • REV 2.0 • ISS 17JUL08