UNITS INSTALLATION
2 Obstacles on discharge side
a. Upper side is open
Single Installation
Front side
Fit positions "
?
N O T E
Mount the airflow guide (*1) and open both right and left sides.
(*1): Optional Part
3 Obstacles on right and left
a. Upper side is open
Single Installation
?
N O T E
If L is higher than H, mount the units on a base so that H is greater or equal to L. H: Unit Height (1650mm) + Base Concrete Height
In this situation ensure that the base is closed and does not allow the airflow to short circuit. In each case, install the outdoor unit so that the
discharge flow is not short-circuited.
8
PMML0390B REV.0 - 11/2015 - P5416649
" with unit back side
?
N O T E
Mount the airflow guide (*1) and
open both right and left sides.
(mm)
L
0 < L < 1/2H
1/2H < L < H
Multiple Installation
?
N O T E
Mount the airflow guide (*1) and open both right and left sides.
b. Obstacles in above
Single Installation
A
600 or more
1400 or more
(mm)
No more than 2 units for
multiple installation
?
N O T E
Mount the airflow guide (*1)
and open both right and left
sides.
(mm)