24 EN – R0...R4 Quick installation guide
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Ensure the cooling
R0-
R4
See table
I
on page
R5
temperature range of the drive is -15 to +50 °C (+5 to +122 °F). No condensation or
frost is allowed. For more information on the ambient temperature and derating, see
R6-
chapter Technical data in ACS580-01 (0.75 to 250 kW) hardware manual
R9
(3AXD50000018826 [English]).
Protect the drive and input power cable
EN
See tables
III
(on page 20) and
fuses.
DA
If you use gG fuses, make sure that the operating time of the fuse is below 0.5
seconds. Follow the local regulations.
DE
Install the drive on the wall
ES
See figure
R0...R4 Figures A
FI
Check the insulation of the power cables and the motor
FR
Check the insulation of the input cable according to local regulations before
IT
connecting it to the drive.
See figure
B1
on page 165.
NL
1. Check the insulation of the motor cable and motor when the cable is disconnected
PL
from the drive. Measure the insulation resistance between each phase conductor
and then between each phase conductor and the Protective Earth conductor
PT
using a measuring voltage of 1000 V DC. The insulation resistance of an ABB
motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the
RU
insulation resistance of other motors, see the manufacturer's instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
SV
moisture is suspected, dry the motor and repeat the measurement.
TR
ZH
19
(UL: table
II
on page 19) for the losses.The allowed operating
IV
(on page 20); (UL: table
on page 165.
V
on page 21) for the