Télécharger Imprimer la page

ABB ACS580-01 Guide D'installation page 23

Variateur

Publicité

EN – R0...R4 Quick installation guide
This guide briefly describes how to install and start-up the drive. For complete
information on installation, see ACS580-01 (0.75 to 250 kW) hardware manual
(3AXD50000018826 [English]). For start-up instructions, see chapter
start-up guide
on page 321.
To read a manual, go to
document number.
Obey the safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur:
If you are not a qualified electrician, do not do electrical installation work.
Do not work on the drive, motor cable or motor when main power is applied. If
the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
Do not work on the control cables when power is applied to the drive or to the
external control circuits.
Make sure that debris from borings and grindings does not enter the drive when
installing.
Make sure that the floor below the drive and the wall where the drive is installed
are non-flammable.
Check if capacitors need to be reformed
If the drive has not been powered (either in storage or unused) for over one year, you
must reform the capacitors.
You can determine the manufacturing time from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY:
13, 14, 15, ... for 2013, 2014, 2015,
WW:
01, 02, 03, ... for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
EN – R0...R4 Quick installation guide 23