N
Code
Name
Br
Baud rate
N17
BMS1
Supervisor
As
Enable Supervisor
N18
BMS1
write commands
Air temperature
N19
LA1
limit 1
Water
N20
St1
temperature
limit 1
Air temperature
N21
LA2
limit 2
Water
N22
St2
temperature
limit 2
Maximum
N23
LSP
settable heating
set point limit
Anti-freeze heater
N24
SRA
setpoint (°C)
Anti-freeze heater
N25
brA
band (°C)
Integrating heater
N26
Sri
setpoint (°C)
Integrating heater
N27
bri
band (°C)
Outside air
N28
tA1
setpoint 1 (°C)
Outside air
N29
tA2
setpoint 2 (°C)
N30
ba
Air band (°C)
Minimum Power
N31
PAS min
in domestic hot
water mode (%)
Maximum Power
N32
PAS max
in domestic hot
water mode (%)
Switching off
N33
OffP
thermostat pump
N34
VP
Fixed pump volts 0.0
Type of multi-
N36
function input
Minimum NTC
probe multi-
N37
function input
value
Maximum NTC
probe multi-
N38
function input
value
Min
Default Max
0
1
2
0
0
1
-25.0
-15.0
45.0
0.0
43
70.0
-25.0
-10.0
45.0
0.0
58.0
70.0
15
55.0
65.0
-20.0
4.0
50.0
0.3
1.0
10.0
0
3.0
70.0
0.0
4.0
20.0
-40.0
5.0
50.0
-40.0
-30.0
50.0
0.0
2.0
20.0
0
50
100
0
100
100
0
0
1
10.0
10.0V
0
0
1
-99.9
0.0
99.9
-99.9
20.0
99.9
Meaning
Baud rate that the supervisor must use in order to communicate with the
control module (8bit data, N-parity, 2 stop bits)
0 – 9600 bps
1 – 19200 bps
2 – 38400 bps
0 - Disables write commands
1 - Enables write commands
The read commands are always enabled.
Enables or excludes only digital commands. Analogue registers are always
available in write mode (cold setpoint, hot setpoint).
If the remote panel is enabled, it has priority. See parameter(9).
Outside air temperature corresponding to the maximum water tempera-
ture (parameter(P)) that can be produced by the compressor.
See paragraph 0.
Maximum water temperature limit that can be produced by the compres-
sor with reference to the air temperature value in the parameter (O).
See paragraph 0.
Outside air temperature corresponding to the maximum water tempera-
ture (parameter(r)) that can be produced by the compressor.
See paragraph 0.
Maximum water temperature limit that can be produced by the compres-
sor with reference to the air temperature value in the parameter (q).
See paragraph 0.
Maximum temperature limit that the user can set as a Hot Setpoint.
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint
entry to adjust the boiler.
If the temperature read by one of the two water probes reaches this value,
the anti-freeze heater is enabled.
If the temperature read by both water probes reaches SrA + brA, the anti-
freeze heater is disabled.
Discrepancy from the Setpoint for water produced in Hot Mode Set_
user(3). See paragraph 4.1.3
Temperature band used with the water setpoint for the integrating heater
in heating mode See paragraph 4.1.3
Below this threshold, the supplementary heater thermostat is activated (it
comes on at Sri and switches off at Sri+bri).
Under this threshold, only the operation of the heater is enabled, not the
one of the compressor.
Band to be applied to the air temperature setpoints.
For units envisaging the domestic hot water production function, once this
function has been activated, it is possible to decide the minimum power
percentage to be used in order to produce domestic hot water.
For units envisaging the domestic hot water production function, once this
function has been activated, it is possible to decide the maximum power
percentage to be used in order to produce domestic hot water.
0 = the pump remains in operation when the setpoint temperature is
reached.
1 = the pump is switched off when the setpoint temperature is reached.
(when this option is selected, the adjustment is activated automatically in
relation to the input temperature).
This parameter is only displayed when adjustment based on input
temperature (parameter(0) =1 or 2). The input water temperature probe
can be a remote unit at 50m from the exterior of the machine in order to
measure the temperature of a storage tank.
Fixed volts for inverter pump on-board the machine. Can be set in relation
to plant features (see pump documentation).
0= NTC input
1= 0-10V input
Minimum value which must be matched by the final result in relation to
the configuration of the multi-function input.
(see parameter N11)
Maximum value which must be matched by the final result in relation to
the configuration of the multi-function input.
(see parameter N11)