BLUEFACE AND THINK THERMOSTATS (AZZBSBLUEFACEC / AZZBSTHINK [C/R])
Blueface and Think Thermostat Warnings
Thermostat displays all the system warnings on the screensaver. If there is any error, it will be displayed on the screensaver, on
the main screen and on
(only Blueface)
Anti-freezing
thermostat, system parameters
Unoccupied Override. A zone has been activated while the user mode is set on Unoccupied. The system will start
using the Comfort Mode during the selected override time. When the override time has expired, the system returns to
its previous status.
Vacation Override. A zone has been activated while the user mode is set on Vacation. The system will start using the
Comfort Mode during the selected override time. When the override time has expired, the system returns to its
previous status.
Window. It indicates the air conditioning of the zone has been deactivated due to open window. Only available if the
window contact of the system is activated.
Global ventilation
Occupancy. It indicates no occupancy has been detected in the zone for the last 5 minutes. Therefore, the Timer
function is activated (the zone will switch off after 90 minutes). Only available for systems with occupancy.
Low Battery Lite
(only Blueface)
Note: For Lite thermostats, the low battery warning will disappear after about 5 minutes from the battery replacement.
(only Think wireless).
Battery
Blueface and Think Thermostats errors
If any type of anomaly is detected, the word "Error" is displayed on the screensaver of these devices. You may find the following
errors:
Error 1: Communication error between wired thermostat and zone module
(AZZBSDAMPERxxC / AZZBSZMRADC / AZZBSZMxxxC)
This incident blocks the control of the zone. To solve this incident check:
1.
Connection: Check the polarity of the connectors of the module and the thermostat.
2.
Wiring: Check that the voltage between the poles (A /-) and (B/-) is about 0.65 Vdc.
3.
Wiring: Verify that the module connection bus-thermostat is not next to low-voltage wiring.
4.
Module: Check the correct operation of the module, for this connect another thermostat and verify that the error
disappears.
5.
Restart the zone and re-associate it with the system:
-
Blueface thermostats: Press on Reset to restart the device. If the error persists, press and hold on
thermostat. Configure the system.
-
Think thermostats: To do this, press and hold on
6.
Restart system: If the system is restarted, this error may be displayed in the thermostats at the beginning of the process.
This message should disappear after around 30 seconds.
tio , inside the User settings menu.
. It will be only displayed when it is activated (See
).
(only Blueface)
. The global ventilation is activated.
. Low battery warning. Informs about the involved zone when the icon is pressed.
Low battery warning.
Advanced Configuration Blueface
and restart the start-up configuration process.
and reset the
44