quart de pouce, un éliminateur de vibrations doit être installé à proximité du compresseur
à moteur dans une position horizontale parallèle au compresseur, au vilebrequin ou dans
une position verticale à 90 degrés par rapport au vilebrequin du compresseur.
NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
compressor.
Split System Interconnecting Line Sizing Chart
Table 3
60Hz Models
Model
Liquid
Line(OD)
¼ inches
CS025
CS050
¼ inches
50Hz Models
Model
Liquid
Line(OD)
WGC60
0.635cm
*Use 1/2" (1,27cm) to 3/8" (0.952cm) reducer at evaporator
Notes:
Line lengths are expressed in equivalent feet = actual run length + fitting
•
allowances (i.e. ~5' for each bend/elbow allowance).
Use only refrigeration grade dehydrated tubing.
•
Install refrigeration piping per local codes and ASHRAE guidelines.
•
43
Suction
Min.
line at
Suction
Condenser
line
(OD)
insulation
thickness
(in)
3/8 inches
3/8 inches
½ inches
3/8 inches
Suction
Min.
line at
Suction
Condenser
line
(OD)
insulation
thickness
(in)
1.27cm
0.952cm
Suction
Maximum
connection
"total" line
at
length
evaporator
(OD)
3/8 inches
50 feet
3/8 inches*
50 feet
Suction
Maximum
connection
"total" line
at
length
evaporator
(OD)
0.952cm*
15.24 meters
Maximum lift
(height)
15 feet
15 feet
Maximum lift
(height)
4.57 meters