Installation remarks / Mounting
• Adhere to the relevant national regulations and provisions.
• Mount the module onto a wired FC lower part and then onto a 35mm rail
or fasten it onto a suitable mounting surface.
• To observe the specified protection class, the 4 screws of the upper part must
be tightened evenly crosswise with 0.8 Nm. When mounting the module
ensure that the seal is carefully inserted. Only use the supplied lower part
and supplied seals. Only use the yellow AS-i flat cable AC4000.
• During installation and laying the bending radii of the cables must be such
that neither the cable entries nor the seals are subjected to mechanical
stress.
Special conditions for safe operation
• Avoid electrostatic charging on plastic units and cables.
• Do not mount the module in the dust flow.
• Avoid dust deposits on the module.
• Avoid electrostatic charging, only clean the unit with a damp cloth. In prin-
ciple, rubbing with non-conductive materials must be avoided.
• Avoid direct radiation with high UV components (sunlight), mount the unit
at a protected place.
• The unit is rated for a low impact energy (EN50021, table 13, 2 joules). Pro-
tect the unit and cable against destruction.
• Insert the blanking seals in the supplied module lower part if the module is
connected at the end of the cable line. The end of the flat cable must be
located inside the module.
• Cover any unused sockets with protective caps (AC3004), tightening torque
0.8 Nm.
• Do not separate the module upper part from the FC lower part while live.
• Do not disconnect the M12 connections while live.
• Use M12 connectors with hexagon nuts, tightening torque 0.8 Nm.
• Check the tightening torque of the screws two weeks after mounting and
retighten them, if necessary.
• Protective caps, housing upper / lower part and M12 nuts may only be opened
or closed in a sufficiently clean environment.
• Using an FC lower part with addressing socket is not permitted.