INSTRUCTION
ED-RU-DOCS
IN20012 REV. B, 2019-03-11
C C a a u u t t i i o o n n ! ! Read and understand the instruction before using the product.
C C a a u u t t i i o o n n ! ! Ensure that the installation complies with local safety
regulations.
C C a a u u t t i i o o n n ! ! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Room unit for basic controller configuration or end-
user control
ED-RU-DOCS is an external room unit primarily intended for control of
an air handling unit, heating unit or room controller.
Perform basic controller configuration, or let the person in the room
control the room's HVAC behaviour, via a connected ED-RU... room
unit. Choose from a large selection of room units that fit your specific
needs.
Technical data
Supply voltage
24 V AC
Power consumption
25 mA
Protection class
IP20
Ambient humidity
Max.90% RH (non-condensing)
Ambient temperature
0...50°C
Storage temperature
-20...+70°C
Mounting
On wall or device box
Display type
Backlit LCD
Communication
EXOline
Measuring range CO
0...5000 ppm
2
Accuracy
400...5000 ppm ± (25 ppm ± 3 % of the measured
value)
Wiring
Based on the used controller there are two different wiring options:
1. The room unit can be connected to the same supply voltage as the
controller (G and G0). Communication then takes place via EXOline
and is connected to the serial ports (RS485), A and B.
G
10
G0
11
42
A
A
B
43
B
Figure 1 Wiring
2. They can also be connected via an EDSP-K3 cable to the display port.
ED-RU
10 G
...
11
G0
42
A
43
B
Figure 2 Wiring with an EDSP-K3 cable
ED-RU-DOCS
Terminal NO and
EDSP-K3 wire color
designator
10 G
Black
11 G0
White
42 A
Yellow
43 B
Brown
Settings
The On/Off button using Application tool
Regio Eedo/Ardo provides several options to manage controller state
changes, that is changes between a comfort and an energy-saving
operational mode. For example, state changes can be managed by:
– Pressing the occupancy button on the room unit to increase the
airflow.
– Detecting presence in the room via a CO
detector.
24 V AC
The On/Off button using E-tool
The function of the On/Off button can be configured using E tool.
Setting
No function
On/Off
On/Off/Extended running
When pressing the On/Off button for 10 s, the air handling unit will
stop. At the next scheduled start-up it will then start and run in mode
AUTO.
A press of the button will start the unit, making it run at normal speed
for the duration set under "extended running" (factory setting 60 min.).
Thereafter, the unit will enter into auto mode.
Increase/Decrease button
Enables adjusting the setpoint up or down. The maximum permissable
adjustment of the setpoint is configurable (factory setting ± 3°C).
Depending on the control mode, the setpoint buttons will adjust the
actual setpoint.
Description
24 V AC supply voltage
input
24 V AC voltage
reference
Output signal to controller
Input signal to controller
sensor or a motion
2
Description
Pressing the button has no effect.
The button can be used to turn the unit
off or place it in auto mode
The button can be used to turn the unit
off or to force it to run in normal speed
for a settable duration, after which it will
enter auto mode.
1

Publicité

loading

Sommaire des Matières pour Regin ED-RU-DOCS

  • Page 1 2. They can also be connected via an EDSP-K3 cable to the display port. ED-RU-DOCS is an external room unit primarily intended for control of A press of the button will start the unit, making it run at normal speed an air handling unit, heating unit or room controller.
  • Page 2 They can be used together with a Regin system matningsspänning Effektförbrukning 25 mA controller, where the setup must be done with Regin's tool for free programmable controllers. All the units have a built-in temperature 11 G0 24 V AC matningsspän-...
  • Page 3: Technische Daten

    Die Taste kann benutzt werden, um die Bild 1 Verdrahtung Anlage auszuschalten, oder sie für eine ED-RU-DOCS ist ein externes Raumgerät, das vor allem für die bestimmte Dauer auf Stufe 2 laufen zu Regelung einer Lüftungsanlage, einer Heizungsanlage oder als lassen, bevor sie dann in den Auto-Mo- 2.
  • Page 4: Caractéristiques Techniques

    24 V AC eingestellt wurde. Danach schaltet die Anlage in den Auto-Modus um. ED-RU-DOCS est une unité d'ambiance externe conçue principalement Erhöhen/Senken-Tasten pour le contrôle d'une unité de traitement d'air, d'une unité de chauffage ou d'un régulateur d'ambiance.
  • Page 5 La gamme ED-RU peut également être utilisée avec les automates librement programmable, dont la programmation s'effectue avec les outils de Regin. Toutes les unités d'ambiance sont dotées d’une sonde de température intégrée. Ce produit porte le marquage CE. Pour plus d'information, veuillez consulter le site web www.regincontrols.com.