Operation
Programming :
Frequency Menu : Threshold detection starts from the loss of source or source return sequence
LCD
Denomination/Definition
Network 1 over frequency threshold
Network 1 over frequency threshold
hysteresis
Network 1 under frequency threshold
Network 1 under frequency threshold
hysteresis
Network 2 over frequency threshold
Network 2 over frequency threshold
hysteresis
Network 2 under frequency threshold
Network 2 under frequency threshold
hysteresis
q
Values definition: % of nominal values Hysteresis values range is limited by thresholds values.
55
All manuals and user guides at all-guides.com
Setting range
from 101 to120%
from 100.5 to119.5%
(< oF)
from 80 to 99%
from 80.5 to 99.5% (> uF)
from 101 to120%
from 100.5 to119.5%
(< oF)
from 80 to 99%
from 80.5 to 99.5% (> uF)
Default value
105 %
103 %
95 %
97 %
105 %
103 %
95 %
97 %