hager HIC4 Serie Notice D'utilisation page 55

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operation
Programming
Parameter Characteristics : Menu (Setup)
Setup
LCD
Denomination
Type of network*
Network nominal
voltage
Network nominal
frequency
Source 1 -
Switch Ior II
configuration
Normally opened
or closed
Network priority
selection
1 2
Manual Retransfer
Type of control
logic selection
Number of
permutation
counter Reset
Programming code
modification
* refer to annexes.
53
All manuals and user guides at all-guides.com
Definition
Number of active conductors
of controlled network
(refer to annexes)
Phase-Neutral voltage
for 1BL & 41NBL
Phase-Phase voltage for others
Network nominal frequency
Source 1 (controlled and
displayed) linked to switch I or II
(depending on cabling)
Normally opened or closed
Keypad selection (1 or 2)
Activation of the feature
Impulse or contactor
Allows source 1 -> source 2
automatic sequences counter
reset
Possible to change the
programming code
Setting range
1BL, 2BL, 2NBL, 3NBL,
4NBL, 41 NBL
from 110 V to 480 V
50Hz ou 60Hz
I, II
NO ou NC
1 ou 2
Yes ou No
Imp, Con
Yes ou No
from 0001 to 9999
Default value
4NBL
400 VAC
50 Hz
I
NO
1
No
Imp
No
1000