Volt Menu : Threshold detection starts from the loss of source or source return sequence
LCD
Denomination/Definition
Network 1 over voltage threshold
Network 1 over voltage threshold
hysteresis
Network 1 under voltage threshold
Network 1 under voltage threshold
hysteresis
Network 2 over voltage threshold
Network 2 over voltage threshold
hysteresis
Network 2 under voltage threshold
Network 2 under voltage threshold
hysteresis
q
Values definition: % of nominal values Hysteresis values range is limited by thresholds values.
54
All manuals and user guides at all-guides.com
Setting range
from 102 to120%
from 101 to119% (<oU)
from 80 to 98%
from 81 to 99%(>uO)
from 102 to120%
from 101 to119% (<oU)
from 80 to 98%
from 81 to 99%(>uU)
Default value
115 %
110 %
85 %
95 %
115 %
110 %
95 %
85 %