Environment
IP-Rating
Temperature
Hygrometry
Altitude
Storage Temperature
Storage Period
Weights
Standards and Directives
Notes
36
All manuals and user guides at all-guides.com
Maximum altitude without de-rating =2000 metres≤630 A≥800 A
It is recommended not to stock the products in a corrosive or salty atmosphere.
The product meets the applicable european directive CE.
The product also meets applicable international directive IEC60947-6-1:
low voltage devices, automatic transfer and connection material.
IP2 and class II for the front face.
-10 +40°C without de-rating
-20 +70°C with de-rating (refer to catalogue)
80% humidity without condensation at 55°C
95% humidity with condensation at 40°C
-20 to +70°C
maximum 1 year.