Permanent signal of output 2,
activated at count value M preset 2
in adding mode and at count value
m zero in subtracting mode*
Permanent signal of output 2, will
become passive at count value M
preset 2 in adding mode and at
count value m zero in subtracting
mode**
Timed signal of output 2, will be-
come passive at count value = pre-
set 2 in adding mode and at count
value = zero in subtracting mode**
Timed signal of output 2, activated
at count value = preset 2 in adding
mode and at count value = zero in
subtracting mode*
Duration of timed signal of output 2,
can be set from 00.01 s to 99.99 s.
* Activation of relay coil resp. opto-
coupler when reaching the preset
value
** Relay coil becomes dead resp.
optocoupler will be locked when
reaching the preset value
6.2.3 Programming routine Frequency Meter
Gate time = within this period the
incoming pulses will be counted
and displayed.
Programmable range from 00.01 s
to 99.99 s
Setting with ¤and ⁄-keys
00.00 won't be accepted
Polarity of the inputs:
pospol: positive polarity (PNP)
switching to +24 V
negpol: negative polarity (NPN)
switching to 0 V
Input modes:
E1: INP A = count input
INP B = count direction input
E2: INP A = count input adding
INP B = count input subtr.
E3: Quadrature input
INP A = count input 0°
INP B = count input 90°
E4: same as E3, but with pulse
doubling.
Each pulse edge of INP A will
be counted.
Scaling factor:
0.0001...9.9999
Setting with ¤and ⁄-keys
Factor 0.0000 won't be accepted
Decimal point
(only optical function):
0
= no decimal point
0.0
= one decimal place
0.00 = two decimal places
0.000 = three decimal places