5. Setting of the operating parameters
a. connect to supply voltage
b. set microswitch "A" (right side of the housing) to "ON"
for a short time. Display will show 1st menu item
"Mode".
c. select required function via ⁄-key
d. press P-key to store selected function/enter data and
to change over to next menu item.
e. select again the required function via ⁄-key resp.
enter data (prescaling factor, duration of timed sig-
nal, gate time, resolution) directly via the two arrow-
keys.
f.
After programming the last menu item (permanent or
timed signal), the programming routine will be left by
pressing the P-key, if microswitch "A" ist set to "OFF".
If it is still set to "ON", the programming routine will
be passed through once again.
A B C D
OFF
ON
6. Setting of the operating mode
6.1 Selection of basic function
After microswitch "A" has been switched to "ON" for a
short time, one of the basic functions will be displayed
as follows:
programming
programming
routine
routine
Impulse Counter
Timer
10
6.2.1 Programming routine Impulse Counter
programming
routine
Frequency Meter
Operating mode Add:
Adding mode
Permanent signal at count value
M preset 1 and at count value
M preset 2
Timed signal at count value M
preset 1 and at count value M
preset 2
Reset to zero
Operating mode Sub:
Subtracting mode
Permanent signal at count value m
preset 1 and at count value m zero
Timed signal at count value m
preset 1 and at count value m zero
Reset to preset 2
Operating mode AddAr:
Adding mode
Permanent signal at count value M
preset 1 or timed signal at count va-
lue = preset 1 and at count value =
preset 2
Automatic reset to zero
Operating mode SubAr:
Subtracting mode
Permanent signal at count value m
preset 1 or timed signal at count va-
lue = preset 1 and at count value =
zero
Automatic reset to preset 2
Operating mode AddbAt:
Adding mode
Timed signal at count value = preset
2 and automatic reset to zero.
A second adding preset counter
(batch counter), programmed preset
value = 1, counts the number of
automatic repetitions of preset 2.
Permanent signal at count value M
preset 1 or timed signal at count va-
lue = preset value 1
The reset key sets both counters to
zero, the reset input only sets the
impulse counter to zero.
Operating mode SubbAt:
Subtracting mode
Timed signal at count value = zero
and automatic reset to preset 2.
Batch counter same as in mode
AddbAt.
The reset key sets the impulse
counter to preset 2 and the batch
counter to zero, the reset input only
sets the impulse counter to preset 2.
Polarity of the inputs:
pospol: positive polarity (PNP)
switching to +24 V
negpol: negative polarity (NPN)
switching to 0 V