Technical Information / Operation / Parameters; Adjustable Parameters - IFM Electronic O1D100 Notice De Montage

Capteur de distance
Masquer les pouces Voir aussi pour O1D100:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical information / Operation / Parameters

Adjustable parameters

Switch point 1 / 2
Limit values at which the outputs change their switching status.
SP2 is only active if OU2 = Hno or Hnc.
Configuration for output 1
2 switching functions are adjustable:
- Hno = hysteresis function / normally open
- Hnc = hysteresis function / normally closed
Configuration for output 2
2 switching functions and 1 analogue signal can be set:
- Hno = hysteresis function / normally open
- H nc = hysteresis function / normally closed
- I = analogue output 4 ... 20 mA
Analogue start point
Measured value at which 4 mA is provided.
ASP is only active if OU2 = I.
Analogue end point
Measured value at which 20 mA is provided.
Minimum distance between ASP and AEP = 100 mm.
AEP is only active if OU2 = I.
The error message "SIZE" is displayed if you try to enter a
distance which is below the minimum distance.
Teach
Selection "sampling rate" or "repeatability"
Setting ranges:
The sampling rate influences the accuracy and vice versa.
High sampling rate → low repeatability.
High repeatability → low sampling rate.
Extended functions
This menu point includes a submenu with more parameters.
Press the Set button briefly to access these parameters which
will be explained on the following pages.
22
All manuals and user guides at all-guides.com
→ Sampling rate 1...50 Hz
→ Repeatability 1...100 mm